Operating instructions

28
Set Point 1 (Cooling Setpoint 1, CSP.1) during the occupied
period while operating under Time Schedule 1 (SCH1). If the
Time Schedule 2 (SCH2) is in use, the unit’s active set point is
based on Cooling Set Point 1 (Cooling Setpoint 1, CSP.1) dur-
ing the occupied period and Cooling Set Point 2 (Cooling Set-
point 2, CSP.2) during the unoccupied period. See Tables 26
and 27.
To configure this option while using a Touch Pilot display:
To change this value, a Control Point Force must be applied.
When configured correctly, Setpoint Control (Setpoint
Control, SP.SE) will indicate Auto.
To configure this option while using a Navigator display:
Set Point 1
— When Set Point Select (Setpoint Select, SP.SE)
is configured to 1 (Setpoint 1), the unit’s active set point is
based on Cooling Set Point 1 (Cooling Setpoint 1, CSP.1).
To configure this option with the Touch Pilot display:
To change this value, a Control Point Force must be applied.
When configured correctly, Setpoint Control will indicate
Setp 1.
To configure this option with the Navigator™ display:
Set Point 2
— When Set Point Select (Setpoint Select, SP.SE)
is configured to 2 (Setpoint 2), the unit’s active set point is
based on Cooling Set Point 2 (Cooling Setpoint 2, CSP.2).
To configure this option with the Touch Pilot™ display:
To change this value, a Control Point Force must be applied.
When configured correctly, Setpoint Control (Status
GENUNIT) will indicate Setp 2.
To configure this option with the Navigator display:
4 to 20 mA Input
— When Set Point Select (Setpoint Select,
SP.SE) is configured to 3 (4-20 mA Setp), the unit’s active set
point is based on an field supplied, external 4 to 20 mA signal
input to the Energy Management Module (EMM). Care should
be taken when interfacing with other manufacturers control
systems, due to power supply differences of full wave bridge
versus half wave rectification. The two different power sup-
plies cannot be mixed. ComfortLink™ controls use half wave
rectification. A signal isolation device should be utilized if a
full wave bridge signal generating device is used.
The following equation is used to control the set point. See
Fig. 20.
Fahrenheit Set Point = 10 + 70(mA – 4)/16 (deg F)
Celsius Set Point = –12.2 + 38.9(mA – 4)/16 (deg C)
To configure this option while using a Touch Pilot display:
To change this value, a Control Point Force must be applied.
When configured correctly, Setpoint Control will indicate 4-
20 mA.
To configure this option while using a Navigator display:
Dual Switch
— When Set Point Select (Setpoint Select,
SP.SE) is configured to 4 (Dual Setp Sw), the unit’s active set
point is based on Cooling Set Point 1 (Cooling Setpoint 1,
CSP.1) when the Dual Set Point switch contact is open and
Cooling Set Point 2 (Cooling Setpoint 2, CSP.2) when it is
closed.
To configure this option while using a Touch Pilot display:
To change this value, a Control Point Force must be applied.
When configured correctly, Setpoint Control will indicate
Setp Sw.
To configure this option while using a Navigator display:
Chilled Water Fluid Type Selection — The chilled
water fluid must be configured. The fluid type must be config-
ured to obtain the proper leaving water set point control range
and freeze protection. The Cooler Fluid Type (Cooler Fluid
Type, FLUD) can be set to water or brine.
FRESH WATERConfigure the unit for Cooler Fluid Type
(Cooler Fluid Type, FLUD) to water for units without brine or
glycol installed in the chilled water loop. The factory default
fluid type is fresh water. Use this option for fresh water sys-
tems. This will allow for a water temperature set point of 38 to
60 F (3.3 to 15.5 C). With water as the selection, the Freeze
Point is fixed at 34 F (1.1 C).
To configure this option with the Touch Pilot display:
To configure this option with the Navigator display:
DISPLAY NAME PATH
LINE
NO.
VALUE
Setpoint select StatusGENUNIT 25 0 (Setpoint Occupied)
ITEM ITEM EXPANSION PATH VALUE
SP.SE Setpoint Select Operating Modes
SLCT Setpoint Occ
DISPLAY NAME PATH
LINE
NO.
VALUE
Setpoint select Status
GENUNIT 25 1 (Set Point 1)
ITEM ITEM EXPANSION PATH VALUE
SP.SE Setpoint Select Operating Modes
SLCT Setpoint 1
DISPLAY NAME PATH
LINE
NO.
VALUE
Setpoint select Status
GENUNIT 25 2 (Set Point 2)
ITEM ITEM EXPANSION PATH VALUE
SP.SE Setpoint Select Operating Modes
SLCT Setpoint 2
DISPLAY NAME PATH
LINE
NO.
VALUE
Setpoint select StatusGENUNIT 25 3 (4-20 mA Input)
ITEM ITEM EXPANSION PATH VALUE
SP.SE Setpoint Select Operating Modes
SLCT 4-20 mA Setp
DISPLAY NAME PATH
LINE
NO.
VALUE
Setpoint select Status
GENUNIT 25
4 (Dual
Setpoint Switch)
ITEM ITEM EXPANSION PATH VALUE
SP.SE Setpoint Select Operating Modes
SLCT
Dual
Setp Sw
DISPLAY
NAME
PATH
LINE
NO.
VALUE
Cooler
Fluid Type
Main Menu
ServiceSERVICE1 1 1 = Water
ITEM ITEM EXPANSION PATH VALUE
FLUD Cooler Fluid Type Configuration
SERV Water