Operating instructions

56
P0010 Start Quick Commissioning
0 Ready to Run
1 Quick Commissioning
30 Factory Setting
NOTE: P0010 must always be set back to ‘0’ before operating
the motor. However if P3900 = 1 is set after commissioning this
is done automatically.
P0100 Operation
0 Power in kW; f default 50 Hz
1 Power in hp; f default 60 Hz
2 Power in kW; f default 60 Hz
NOTE: Settings 0 and 1 should be changed using the DIP
switches to allow permanent setting.
P0304 Rated Motor Voltage*
10 V — 2000 V
Nominal motor voltage (V) from rating plate
P0305 Rated Motor Current*
0 — 2 x inverter rated current (A)
Nominal motor current (A) from rating plate
P0307 Rated Motor Power*
0 kW — 2000 kW
Nominal motor power (kW) from rating plate.
If P0100 = 1, values will be in hp
P0310 Rated Motor Frequency*
12 Hz — 650 Hz
Nominal motor frequency (Hz) from rating plate
P0311 Rated Motor Speed*
0 — 4000 1/min
Nominal motor speed (rpm) from rating plate
P0700 Selection of Command Source
(on/off/reverse)
0 Factory Setting
1 Basic Operator Panel
2 Terminal/Digital Inputs
P1000 Selection of Frequency Setpoint
0 No frequency setpoint
1 Operator panel frequency control 
2 Analog Setpoint
P1080 Min. Motor Frequency
Sets minimum motor frequency (0-650Hz) at which the motor
will run independent of the frequency setpoint. The value set
here is valid for both clockwise and counterclockwise rotation.
P1082 Max. Motor Frequency
Sets maximum motor frequency (0-650Hz) at which the motor
will run at independent of the frequency setpoint. The value set
here is valid for both clockwise and counterclockwise rotation.
P1120 Ramp-Up Time
0 s - 650 s
Time taken for the motor to accelerate from standstill up to
maximum motor frequency.
P1121 Ramp-Down Time
0 s - 650 s
Time taken for motor to decelerate from maximum motor
frequency down to a standstill.
P3900 End Quick Commissioning
0 End Quick Commissioning without motor calculation or
factory reset.
1 End Quick Commissioning with motor calculation and
factory reset (Recommended)
2 End Quick Commissioning with motor calculation and with
I/O reset
3 End Quick Commissioning with motor calculation but
without I/O reset
*Motor-specific parameters — see motor rating plate.
NOTE: Shaded boxes are for reference only.
Fig. 36 — Siemens Low Ambient Temperature Controller Flow Chart Quick Commissioning