Specifications

112
APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)
MODE — SERVICE TEST
ITEM EXPANSION UNITS RANGE COMMENT
WRITE
STATUS
CCN TABLE CCN POINT
PAGE
NO.
TEST MANUAL TEST MODE Remote-Off-
Enable Switch
must be set to
OFF Position
Remote-Off-
Enable Switch
must be set to
ENABLE
Position
Not supported.
N/A
T.REQ Manual Sequence OFF/ON forcible N/A service_test 67, 88
CP.A Compressor A Output
OFF/ON
forcible N/A comp_serv_a
SLI.A Slide Valve Capacity A unchanged
increase
decrease
forcible comp_ser_sid_a
CP.B Compressor B Output OFF/ON forcible N/A comp_serv_b
SLI.B Slide Valve Capacity B unchanged
increase
decrease
forcible comp_ser_sid_b
CP.C Compressor C Output OFF/ON forcible N/A comp_serv_c
SLI.C Slide Valve Capacity C unchanged
increase
decrease
Not supported. forcible comp_ser_sid_c
QUIC QUICK TEST MODE Remote-Off-
Enable Switch
must be set to
OFF Position
Not supported.
Not supported.
Not supported.
N/A
Q.REQ OFF/ON forcible N/A 88
EXV.A Circuit A EXV % Open XXX (%) 0-100 forcible N/A 66,67
EXV.B Circuit B EXV % Open XXX (%) 0-100 forcible N/A 66,67
EXV.C Circuit C EXV % Open XXX (%) 0-100 forcible N/A
ECO.A Circ A ECO EXV % XXX (%) 0-100 forcible 67
ECO.B Circ B ECO EXV % XXX (%) 0-100 forcible 67
ECO.C Circ C ECO EXV % XXX (%) 0-100 forcible
FAN.A Circuit A Fan Stages X 0-8 forcible N/A
FAN.B Circuit B Fan Stages X 0-8 Not supported. forcible N/A
FAN.C Circuit C Fan Stages X 0-8 Not supported. forcible N/A
SPD.A Cir A Varifan position XXX (%) 0-100 Not supported. forcible N/A
SPD.B Cir B Varifan position XXX (%) 0-100 Not supported. forcible N/A
SPD.C Cir C Varifan position XXX (%) 0-100 Not supported. forcible N/A
HT.A Oil Heater Circuit A OFF/ON Not supported. forcible
SL1.A Slide Valve 1 Cir A OFF/ON forcible
SL2.A Slide Valve 2 Cir B OFF/ON forcible
HGP.A Hot Gas Bypass A Output OFF/ON forcible
OLS.A Oil Solenoid Cir A OFF/ON forcible
DGT.A DGT Cool Solenoid A OFF/ON forcible
HT.B Oil Heater Circuit B OFF/ON forcible
SL1.B Slide Valve 1 Cir B OFF/ON forcible
SL2.B Slide Valve 2 Cir B OFF/ON forcible
HGP.B Hot Gas Bypass B Output OFF/ON forcible
OLS.B Oil Solenoid Cir A OFF/ON forcible
DGT.B
DGT Cool Solenoid B OFF/ON forcible
HT.C Oil Heater Circuit C OFF/ON Not supported. forcible
SL1.C Slide Valve 1 Cir C OFF/ON Not supported. forcible
SL2.C Slide Valve 2 Cir C OFF/ON Not supported. forcible
HGP.C Hot Gas Bypass C Output OFF/ON Not supported. forcible
OLS.C Oil Solenoid Cir C OFF/ON Not supported. forcible
DGT.C DGT Cool Solenoid C OFF/ON Not supported. forcible
PMP.1 Water Exchanger Pump 1 OFF/ON forcible N/A
PMP.2 Water Exchanger Pump 2 OFF/ON forcible N/A
PMP.3 Condenser Pump 1 OFF/ON forcible
CL.HT Cooler Heater Output OFF/ON Not supported. N/A
BVL.A Ball Valve Position A OPEN/CLSE Not supported.
BVL.B Ball Valve Position B OPEN/CLSE Not supported.
BVL.C Ball Valve Position C OPEN/CLSE Not supported.
Q.RDY Chiller Ready Status OFF/ON forcible N/A
Q.RUN Chiller Running Status OFF/ON forcible N/A
SHUT Customer Shutdown Stat OFF/ON forcible N/A
CATO Chiller Capacity in 0-10v XX.X (vdc) forcible N/A
ALRM Alarm Relay OFF/ON forcible N/A 73
ALRT Alert Relay OFF/ON forcible N/A