APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM EXPANSION UNITS RANGE COMMENT DEFAULT CCN TABLE CCN POINT PAGE NO.
OPTN OPTIONS CONFIGURATION
CCNA CCN Address XXX 1-239 1 N/A CCNA
CCNB CCN Bus Number XXX 0-239 0 N/A CCNB
BAUD CCN Baud Rate 2400
4800
9600
19200
38400
9600 N/A BAUD
LOAD Loading Sequence Select Equal
Staged
EQUAL USER lead_cir 31
LLCS Lead/Lag Circuit Select Automatic
Cir A Leads
Cir B Leads
Cir C Leads
AUTOMATIC USER seq_typ 30
RL.S Ramp Load Select ENBL/DSBL DSBL USER ramp_sel 36
DELY Minutes Off Time XX (Minutes) 1 to 15 1 USER off_on_d 30
ICE.M Ice Mode Enable ENBL/DSBL DSBL USER ice_cnfg 41
HPUM Condenser Pumps Sequence No Pump
1 Pump Only
2 Pumps Auto
PMP 1 Manual
PMP 2 Manual
Not supported.
Not supported.
Not supported.
NO PUMP hpum_seq 30
PUMP Cooler Pumps Sequence No Pump
1 Pump Only
2 Pumps Auto
PMP 1 Manual
PMP 2 Manual
NO PUMP USER pump_seq 29, 30
ROT.P Pump Rotation Delay XXXX (hours) 24 to 3000 48 USER pump_del 30, 59, 60
PM.PS Periodic Pump Start NO-YES NO USER pump_per 29, 30, 60
P.S BY Stop Pump In Standby NO-YES NO USER pump_sby
P.L OC Flow Checked if Pmp Off NO-YES NO USER pump_loc 29, 30
LS.ST Night Low Noise Start XX.XX 00.00-23.59 00.00 USER nh_start
LS.ND Night Low Noise End XX.XX 00-00-23.59 00.00 USER nh_end
LS.LT Low Noise Capacity Lim XXX (%) 0-100 100 USER nh_limit
RV.AL Reverse Alarms Relay NO-YES NO USER al_rever
OA.TH Heat Mode OAT Threshold XX.X
(deg F/deg C)
Not supported. 5 F USER heat_th
CUR.S Current Limit Select NO/YES NO USER curr_sel 40, 41
CUR.F Current Limit at 100% XXXX 0 to 5000 2000 USER curr_ful 40, 41
RSET RESET, DEMAND LIMIT, MASTER/SLAVE
CRST Cooling Reset Type No Reset
Out Air Temp
Delta T Temp
4-20 mA Input
Space Temp
NO RESET USER cr_sel 36, 37, 59
HRST Heating Reset Type No Reset
Out Air Temp
Delta T Temp
4-20 mA Input
NO RESET USER hr_sel
DMDC Demand Limit Select None
Switch
4-20 mA Input
NONE USER lim_sel 40, 41, 59
DMMX mA for 100% Demand Limit XX.X (mA) 0.0 USER lim_mx 41
DMZE mA for 0% Demand Limit XX.X (mA) 0.0 USER lim_ze 41
MSSL Master/Slave Select Disable
Master
Slave
DISABLE MST_SLV ms_sel 32-35
SLVA Slave Address XXX 1-236 2 MST_SLV slv_addr 32-35
LLBL Lead/Lag Balance Select Always Lead
Lag if Fail
Runtime Sel
Always
Lead
MST_SLV ll_bal 32-35, 58
LLBD Lead/Lag Balance Delta XXX (hours) 40-400 168 MST_SLV ll_bal_d 31-35, 58
LLDY Lead/Lag Delay XX (minutes) 2-30 10 MST_SLV lsrt_tim 31-35, 58
LL.ER Start if Error Higher XX.X
(deg F/deg C)
3-18 4 MST_SLV start_dt 31-35
LAG.M Lag Minimum Running Time XXX
(min)
0-150 0 MST_SLV lag_mini 31-35
LAGP Lag Unit Pump Select OFF if U stp
ON if U stp
OFF if U stp MST_SLV lag_pump 31-35, 58
LPUL Lead Pulldown Time XX (minutes) 0-60 0 MST_SLV lead_pul 31-35, 58
SERI Chillers in Series NO/YES NO MST_SLV ll_serie 31-35