For the Navigator™ display, the status of the operating
modes can be found in the MODE submenu under the OPER-
ATING MODES menu. The 6 top priority operating modes are
displayed in MD01 through MD06. To view the modes with
the Navigator™ display:
See Table 37 for a list of operating modes.
STARTUP DELAY IN EFFECT — This mode is checked
for when the unit is started. This mode is active when the Min-
utes Off Time (Unit Off to On Delay, DELY) timer is active.
The unit will not start until the timer has expired. The mode
will terminate when the timer expires.
SECOND SETPOINT IN USE — This mode is checked for
when the unit is ON. The mode is active when Cooling Set-
point 2 (Cooling Setpoint 2, CSP.2) or Ice Setpoint (Cooling
Ice Setpoint, CSP.3) is in use. While in this mode, the Active
Setpoint (Current Setpoint, SETP) will show the CSP.2 or
CSP.3 value.
While in this mode, the unit will operate to the Cooling Set-
point 2 (CSP.2) or Ice Setpoint (CSP.3). The mode will termi-
nate when the Cooling Setpoint 2 (CSP.2) or Ice Setpoint
(CSP.3) is no longer in use.
RESET IN EFFECT This mode is checked for when the
unit is ON. The mode will be active when Temperature Reset
(Cooling Reset Select, CRST) is enabled either by CRST=1
(Outside Air Temperature), CRST=2 (Return Water), CRST=3
(4-20 mA Input), or CRST=4 (Space Temperature) and reset is
active.
While in this mode, the Active Setpoint (Current Setpoint,
SETP) will be modified according to the programmed infor-
mation and will be displayed as the Control Point (Control
Point, CTPT). The mode will terminate when the Temperature
Reset is not modifying the active leaving water set point, caus-
ing SETP to be the same as CTPT.
DEMAND LIMIT ACTIVE This mode is checked for
when the unit is ON. The mode is active when Demand Limit
(Demand Limit Type Select, DMDC) is enabled either by
DMDC=1 (Switch), DMDC=2 (4-20 mA Input), or the Night
Time Low Sound Capacity Limit (
Capacity Limit, LS.LT).
The Active Demand Limit Value (Active Demand Limit
Val, LIM) will display the current demand limit according to
the programmed information and the unit’s capacity will be re-
duced to the amount shown or lower. The mode will terminate
when the Demand Limit command has been removed.
RAMP LOADING ACTIVE This mode is checked for
when the unit is ON. The mode is active when Ramp Loading
(Ramp Loading Select, RL.S) is enabled and the following
conditions are met:
1. The leaving water temperature is more than 4° F (2.2° C)
from the Control Point (Control Point, CTPT), and
2. The rate of change of the leaving water temperature is
greater than the Cool Ramp Loading (Cooling Ramp
Loading, CRMP).
The control will limit the percent capacity increase until one
of the two conditions above are no longer met, then the mode
will terminate.
COOLER PUMPS ROTATION — This mode is checked for
whether the unit is ON or OFF. The mode is active when the
Cooler Pump Sequence (Cooler Pump Run Status,
PUMP=2) (2 Pumps Automatic Changeover) and the Pump
Rotation Delta Timer (Pump Auto Rotation Delay, ROT.P)
have expired.
The control will switch the operation of the pumps. The
lead pump will operate normally. The lag pump will be started,
becoming the lead, and then the original lead pump will be shut
down. This mode will terminate when the pump operation has
been completed.
Table 37 — 30XW Operating Modes
*Not applicable.
ITEM ITEM EXPANSION PATH VALUE
MD01 First Active Mode Operating modes MODE 0-32
MD02 Second Active Mode Operating modes MODE 0-32
MD03 Third Active Mode Operating modes MODE 0-32
MD04 Fourth Active Mode Operating modes MODE 0-32
MD05 Fifth Active Mode Operating modes MODE 0-32
MD06 Sixth Active Mode Operating modes MODE 0-32
NAVIGATOR OPERATING
MODE NUMBER
NAVIGATOR EXPANSION TOUCH PILOT DISCRIPTION
TOUCH PILOT
LINE NUMBER
TOUCH PILOT
VALUE
01 Startup Delay in Effect Startup Delay in Effect 2 Yes/No
02 Second Setpoint in Use Second Setpoint in Use 3 Yes/No
03 Reset in Effect Reset in Effect 4 Yes/No
04 Demand Limit Active Demand Limit Active 5 Yes/No
05 Ramp Loading Active Ramp Loading Active 6 Yes/No
06 Cooler Heater Active* Cooler Heater Active 7 Yes/No
07 Cooler Pumps Rotation Cooler Pumps Rotation 8 Yes/No
08 Pump Periodic Start Pump Periodic Start 9 Yes/No
10 System Manager Active System Manager Active 11 Yes/No
11 Mast Slave Ctrl Active Mast Slave Active 12 Yes/No
12 Auto Changeover Active Auto Changeover Active 13 Yes/No
13 Free Cooling Active Free Cooling Active 14 Yes/No
14 Reclaim Active Reclaim Active 15 Yes/No
15 Electric Heat Active Electric Heat Active 16 Yes/No
16 Heating Low EWT Lockout Heating Low EWT Lockout 17 Yes/No
17 Condenser Pumps Rotation Condenser Pumps Rotation 18 Yes/No
18 Ice Mode in Effect Ice Mode in Effect 19 Yes/No
19 Defrost Active on Cir A Defrost Active on Cir A 20 Yes/No
20 Defrost Active on Cir B Defrost Active on Cir B 21 Yes/No
21 Low Suction Circuit A Low Suction Circuit A 22 Yes/No
22 Low Suction Circuit B Low Suction Circuit B 23 Yes/No
24 High DGT Circuit A High DGT Circuit A 25 Yes/No
25 High DGT Circuit B High DGT Circuit B 26 Yes/No
27 High Pres Override Cir A High Pres Override Cir A 28 Yes/No
28 High Pres Override Cir B High Pres Override Cir B 29 Yes/No
30 Low Superheat Circuit A Low Superheat Circuit A 31 Yes/No
31 Low Superheat Circuit B Low Superheat Circuit B 32 Yes/No