Specifications

76
Table 50 — Alarm Codes (cont)
LEGEND
* Not applicable.
PREFIX
CODE
SUFFIX
CODE
ALARM
NUMBER
ALARM DESCRIPTION REASON FOR ALARM
ACTION TAKEN
BY CONTROL
RESET
TYPE
PROBABLE CAUSE
Pr 01 26 Circuit A Discharge
Transducer
Measured voltage is
0 vdc or SST > EWT and
EXV < 50% for 1 minute
Circuit shut down or
not allowed to start
Automatic Faulty transducer,
wiring error, failed main
base board or
fan board
02 27 Circuit B Discharge
Transducer
04 29 Circuit A Suction Transducer
05 30 Circuit B Suction Transducer
07* 32* Circuit A Reclaim Pumpdown
Pressure Transducer
None
Automatic
Configuration error
08* 33* Circuit B Reclaim Pumpdown
Pressure Transducer
10 34 Circuit A Oil Pressure
Transducer
Circuit shut down or
not allowed to start
Automatic
Faulty transducer,
wiring error, failed CPM
board
11 35 Circuit B Oil Pressure
Transducer
13 37 Circuit A Economizer
Pressure Transducer
Measured voltage is
0 vdc
Circuit shut down or
not allowed to start
Automatic
Faulty transducer,
wiring error, failed CPM
board
14 38 Circuit B Economizer
Pressure Transducer
Co A1 53 Loss of communication with
Compressor Board A
No communication
with CPM board
Affected
compressor shut
down
Automatic Wrong CPM address,
wrong unit configura-
tion, wiring error, power
loss, failed
CPM board
B1 54 Loss of communication with
Compressor Board B
E1 56 Loss of communication with
EXV Board 1
No communication with
EXV board
Affected
compressor
shut down
Automatic Wrong EXV board
address, wrong unit
configuration, wiring
error, power loss,
failed EXV board
E2 57 Loss of communication with
EXV Board 2
03 64 Loss of communication with
Energy Management Board
No communication with
EMM board
Disable or not allow
EMM functions
3 step and 4-20 mA
and space tempera-
ture reset, occu-
pancy override and
ice build)
Automatic Wrong board
address, wrong unit
configuration, wiring
error, power loss to
module, failed module
05 66 Loss of communication with
AUX Board 6
No communication
with MLV/COND Board
Unit shut down or
not allowed to start
Automatic
Wrong board
address, wrong unit
configuration, wiring
error, power loss to
module, failed module
P 01 67 Cooler Freeze Protection Entering or leaving therm-
istor sensed a tempera-
ture at or below freeze
point
Unit shut down or
not allowed to start
Automatic, first
occurrence in
24 hours;
manual if
multiple alarms
within 24 hours
Faulty thermistor, faulty
wiring, low water flow,
low loop volume, fouled
cooler, or freeze
conditions
02 68 Condenser Freeze Protection
Circuit A
03 69 Condenser Freeze Protection
Circuit B
05 71 Circuit A Low Suction
Temperature
Low saturated suction
temperatures detected for
a period of time
Circuit shut down Automatic, first
occurrence in
24 hours;
manual if
multiple alarms
within 24 hours
Faulty thermistor, faulty
wiring, low water flow,
low loop volume, fouled
cooler, or freeze
conditions
06 72 Circuit B Low Suction
Temperature
08 74 Circuit A High Suction
Superheat
EXV>98%,
suction superheat > 30 F,
and SST<MOP for more
than 5 minutes
Circuit shut down Manual Faulty transducer,
faulty wiring, faulty
thermistor, faulty EXV,
low refrigerant charge,
plugged or restricted
liquid line
09 75 Circuit B High Suction
Superheat
CCN Carrier Comfort Network
®
MBB Main Base Board
CPM Compressor Protection Module MLV Minimum Load Valve
EMM Energy Management Module MOP Maximum Operating Pressure
EWT Entering Water Temperature MTA Must Trip Amps
EXV Electronic Expansion Valve SST Saturated Suction Temperature
HPS High Pressure Switch UL Underwriters Laboratories
LWT Leaving Water Temperature