Specifications

82
EXV operation
liquid line refrigerant restriction, filter drier, service valve,
etc
refrigerant charge
If the Leaving Water Set Point is above 40 F (4.4 C) and
there is glycol in the loop, consider using the Medium
Temperature Brine option (Cooler Fluid Type, FLUD=2)
to utilize the brine freeze point instead of 34 F (1.1 C).
High Suction Superheat
Alarm 74 — Circuit A (P.08)
Alarm 75 — Circuit B (P.09)
Criteria for Trip — The criteria are tested only when the cir-
cuit is ON. This alarm is generated if all of the following crite-
ria are met:
The EXV position is equal to or greater than 98%.
The circuit’s Suction Superheat (Suction Gas Temperature –
Saturated Suction Temperature) is greater than the super-
heat control set point.
The circuit’s Saturated Suction Temperature is less than
Maximum Operating Pressure (MOP) set point (EXV
MOP Setpoint, MOP) for more than 5 minutes.
Action to be Taken — The circuit is shut down normally.
Reset Method — Manual.
Possible Causes — If this condition is encountered, check the
following items:
suction pressure transducer wiring to Main Base Board
board for a faulty channel
a faulty suction transducer
suction gas thermistor wiring to EXV Board 1 or to EXV
Board 2
suction gas thermistor sensor for accuracy
for EXV Board 1 or EXV Board 2 faulty channel
EXV operation
a liquid line refrigerant restriction, filter drier, service valve,
etc.
refrigerant charge
Low Suction Superheat
Alarm 77 — Circuit A (P.11)
Alarm 78 — Circuit B (P.12)
Criteria for Trip — The criteria are tested when the circuit is
ON. This alarm is generated if the following criterion is met:
The EXV position is equal to or less than 5% and the cir-
cuit’s Suction Superheat (Suction Gas Temperature – Saturated
Suction Temperature) is less than the Suction Superheat Set
Point (EXVA Superheat Setpoint, SHP.A, EXVB Superheat
Setpoint, SHP.B, or EXVC Superheat Setpoint, SHP.C) by at
least 5° F (2.8° C) or the circuit Saturated Suction Temperature
is greater than Maximum Operating Pressure (MOP) set point
(EXV MOP Setpoint, MOP) for more than 5 minutes.
Action to be Taken — The circuit is shut down normally.
Reset Method — Automatic, first occurrence in 24 hours.
Manual, if more than one occurrence in 24 hours.
Possible Causes — If this condition is encountered, check the
following items:
suction pressure transducer wiring to Main Base Board
board for a faulty channel
faulty suction transducer
suction gas thermistor wiring to EXV Board 1 or to EXV
Board 2
suction gas thermistor sensor for accuracy
EXV Board 1 or EXV Board 2 faulty channel
EXV operation
confirm maximum operating pressure set point
refrigerant charge level
Alarm 80 — Interlock Failure (P.14)
Criteria for Trip — The criteria are tested whether the unit is
ON or OFF. This alarm is generated if the lockout switch
(located in the Energy Management Module) is closed during
normal operation.
Action to be Taken — All compressors are shut down immedi-
ately without going through the normal sequence and are not
allowed to start.
Reset Method — Automatic, first occurrence in 24 hours.
Manual, if more than one occurrence in 24 hours.
Possible Causes — If this condition is encountered, check the
following items:
chilled water flow switch operation
water flow. Be sure all water isolation valves are open and
check water strainer for a restriction
interlock wiring circuit
power supply to the pump
control signal to the pump controller
chilled water pump operation
cooler pump contactor for proper operation
Alarm 81 — Electrical Box Thermostat Failure/Reverse
Rotation (P.28)
Criteria for Trip — The alarm criteria are checked whether the
unit is ON or OFF. If channel 15A on the MBB, which is used
for field wired external pump interlock, is open then the alarm
will be generated.
Action to be Taken — Unit shut down or note allowed to start.
Reset Method — Automatic, if the channel is closed, the unit
will start normally.
Possible Causes — If this condition is encountered, check the
following items:
jumper wiring on TB5-1 and TB5-2 when channel is not in
use
external pump interlock open
field wiring for the external pump interlock open
Alarm 82 — Loss of Communication with System Manager
(P.29)
Criteria for Trip — The criterion is tested whether the unit is
ON or OFF. This alarm is generated if the System Manager
had established communications with the machine and is then
lost for more than 2 minutes.
Action to be Taken — The action to be taken by the control
depends on the configuration. If Auto Start when SM lost is
enabled, (Cooler Heater Delta Spt, AU.SM=YES), then the
unit will force the CCN Chiller Start Stop to ENBL and clear
all forced points from the System Manager. The unit will revert
to stand-alone operation.
Reset Method — Automatic, once communication is
re-established.
Possible Causes — If this condition is encountered, check the
following items:
communication wiring
power supply to the System Manager and unit controls
Alarm 83 — Master/Slave Communication Failure (P.30)
Criteria for Trip — The criterion is tested whether the units are
ON or OFF and a master and slave machine has been config-
ured, (Master/Slave Select, MSSL=1 and Master/Slave
Select, MSSL=2). If communication is lost for more than 3
minutes, this alarm is generated.
Action to be Taken — Dual chiller control will be disabled and
each unit will operate in Stand-Alone mode.
Reset Method — Automatic, once communication is
re-established.
Possible Causes — If this condition is encountered, check the
following items:
CCN wiring
control power to each Main Base Board, master and slave
confirm correct configuration