Specifications

13
Table 8 — Thermistors and Wells
To connect the space temperature sensor (Fig. 8):
1. Using a 20 AWG twisted pair conductor cable rated for
the application, connect 1 wire of the twisted pair to one
SEN terminal and connect the other wire to the other
SEN terminal located under the cover of the space
temperature sensor.
2. Connect the other ends of the wires to terminals 3 and 4
on LVT located in the unit control box.
Units on the CCN can be monitored from the space at the
sensor through the RJ11 connector, if desired. To wire the RJ11
connector into the CCN (Fig. 9):
THERMISTOR
PART NO.
DESCRIPTION WELL PART NO.
HH79NZ014
3 in., 5,000 ohm
Thermistor
1DHB50106801
HH79NZ029
4 in., 5,000 ohm
Thermistor
1DHB50106802
IMPORTANT: The cable selected for the RJ11 connector
wiring MUST be identical to the CCN communication bus
wire used for the entire network. Refer to Table 7 for
acceptable wiring.
CEPL130346-01