APPENDIX A — LOCAL DISPLAY TABLES
Run Status Mode and Sub-Mode Directory
* If these devices are not installed, they will not show in the table.
Service Test Mode and Sub-Mode Directory
ITEM EXPANSION RANGE UNITS CCN POINT COMMENT
VIEW AUTO VIEW OF RUN STATUS
EWT Entering Fluid Temp xxx.x °F (°C) EWT
LWT Leaving Fluid Temp xxx.x °F (°C) LWT
SETP Active Setpoint xxx.x °F SP
CTPT Control Point xxx.x °F CTRL_PNT
LOD.F Load/Unload Factor xxx SMZ
STAT Control Mode x STAT
OCC Occupied NO/YES OCC
MODE Override Modes in Effect NO/YES MODE
CAP Percent Total Capacity xxx CAP_T
DEM.L Active Demand Limit DEM_LIM
STGE Requested Stage x STAGE
ALRM Current Alarms and Alerts xxx ALRMALRT
TIME Time of Day 00:00-23:59 xx.xx TIMECOPY
MNTH Month of Year 1 - 12
(1 = January,
2 = February, etc.)
xx MOY
DATE Day of Month 01-31 xx DOM
YEAR Year of Century xx YOCDISP
RUN UNIT RUN HOUR AND START
HRS.U Machine Operating Hours 0 to 999999 xxxx HRS HR_MACH
STR.U Machine Starts 0 to 1000000 xxxx CY_MACH
HR.P1 Cooler Pump Run Hours 0 to 999999.9 xxxx HRS HR_CPUMP
HR.P2 Condenser Pump Run Hours 0 to 999999.9 xxxx HRS HR_DPUMP
HOUR CIRC AND COMP RUN HOURS
HR.A1 Compressor A1 Run Hours 0 to 999999 xxxx HRS HOURS_A1
HR.A2 Compressor A2 Run Hours 0 to 999999 xxxx HRS HOURS_A2
HR.A3 Compressor A3 Run Hours 0 to 999999 xxxx HRS HOURS_A3
STRT COMPRESSOR STARTS
ST.A1 Compressor A1 Starts 0 to 999999 xxxx CY_A1
ST.A2 Compressor A2 Starts 0 to 999999 xxxx CY_A2
ST.A3 Compressor A3 Starts 0 to 999999 xxxx CY_A3
PM PREVENTIVE MAINTENANCE
STRN STRAINER MAINTENANCE
STRN
SI.ST Strainer Srvc Interval xxxx HRS SI_STRNR
STRN
S.T.DN Strainer Srvc Countdown 0 to 65535 xxxx HRS ST_CDOWN Default: 8760
STRN
S.T.MN Strainer Maint. Done 0 to 65535 NO/YES ST_MAINT
ST.DT STRAINER MAINT. DATES
ST.DT
S.T.M0 MM/DD/YY HH:MM
ST.DT
S.T.M1 MM/DD/YY HH:MM
ST.DT
S.T.M2 MM/DD/YY HH:MM
ST.DT
S.T.M3 MM/DD/YY HH:MM
ST.DT
S.T.M4 MM/DD/YY HH:MM
VERS SOFTWARE VERSION NUMBERS
MBB CESR131482-xx-xx
AUX1* CESR131333-xx-xx
EMM* CESR131174-xx-xx
MARQ CESR131171-xx-xx
NAVI* CESR130227-xx-xx
ITEM EXPANSION RANGE UNITS CCN POINT COMMENT
TEST SERVICE TEST MODE OFF/ON MAN_CTRL To enable Service Test
mode, move Enable/Off/
Remote contact switch to
OFF. Change TEST to
ON. Move switch to
ENABLE.
OUTS OUTPUTS AND PUMPS
CLR.P Cooler Pump Relay OFF/ON S_CLPMP
CND.P Condenser Pump OFF/ON S_CNDPMP
UL.TM Comp A1 Unload Time 0 to 15 xx S_A1ULTM
CC.H Crankcase Heater OFF/ON S_CCH
CW.VO Condenser Valve Open OFF/ON S_CWVO not supported
CW.VC Condenser Valve Close OFF/ON S_CWVC not supported
LL.SV Liquid Line Solenoid OFF/ON S_LLSV
RMT.A Remote Alarm Relay OFF/ON S_ALM
CMPA CIRCUIT 1 COMPRESSOR TST
CC.A1 Compressor A1 Relay OFF/ON S_A1_RLY
UL.TM Comp A1 Unload Time 0 to 15 xx S_A1ULTM
CC.A2 Compressor A2 Relay OFF/ON S_A2_RLY
CC.A3 Compressor A3 Relay OFF/ON S_A3_RLY
MLV Minimum Load Valve Relay OFF/ON S_MLV