Specifications

53
APPENDIX A — LOCAL DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT
DISP DISPLAY CONFIGURATION
TEST Test Display LEDs OFF/ON DISPTEST
METR Metric Display OFF = English
ON = Metric
DISPUNIT OFF = English
LANG Language Selection 0 = English
1 = Espanol
2 = Francais
3 = Portuguese
XLANGUAGE0
PAS . E Password Enable DSBL/ENBL PASS_EBL ENBL
PAS S Service Password 0 to 9999 XXXX PASSCOPY 1111
UNIT UNIT CONFIGURATION
TYPE Unit Type
2=Air Cooled,
3=Water Cooled
XUNIT_TYP
SIZE Unit Size 15 to 45 XXX SIZE
SZA.1 Compressor A1 Size Unit Size Depen-
dent
XX SIZE_A1
SZA.2 Compressor A2 Size Unit Size Depen-
dent
XX SIZE_A2
SZA.3 Compressor A3 Size Unit Size Depen-
dent
XX SIZE_A3
A1.TY Compressor A1 Digital? NO/YES CPA1TYPE
MAX.T Maximum A1 Unload Time 0 to 15 XX MAXULTME 7 (040,045)
10 (015,020,030)
OPT1 UNIT OPTIONS 1 HARDWARE
FLUD Cooler Fluid
1 = Water
2 = Medium Temp
Brine
X FLUIDTYP 1 = Water
MLV.S Minimum Load Vlv Select NO/YES MLV_FLG NO
RG.EN Return Gas Sensor Enable DSBL/ENBL RGT_ENA
OAT.E Enable OAT Sensor DSBL/ENBL OAT_ENA
CSB.E CSB Boards Enable DSBL/ENBL CSB_ENA
CPC Cooler Pump Control OFF/ON CPC ON
PM.DY Cooler Pump Shutdown Dly 0 to 10 XX MIN PUMP_DLY 1 MIN
D.PM.E Enable Condenser Pump 0=No Control
1=On When Occu-
pied
2=On with Com-
pressors
X CONDPMPE 0=No Control
D.FL.S Enable Cond Flow Switch DSBL/ENBL CONDFLSW DSBL
CDWS Enable Cond Wtr Sensors DSBL/ENBL CONDWTRS DSBL
OPT2 UNIT OPTIONS 2 CONTROLS
CTRL Control Method 0=Switch
1=Occupancy
2=Occupancy
3=CCN
X CONTROL 0=Switch
LCWT High LCW Alert Limit 2 to 60°F
(1.1 to 33.3°C)
XX LCW_LMT 60°F (33.3°C)
DELY Minutes Off Time 0 to 15 XX DELAY 0
ICE.M Ice Mode Enable DSBL/ENBL
(Requires EMM)
ICE_CNFG DSBL
CCN CCN NETWORK CONFIGS
CCNA CCN Address 1 to 239 XXX CCNADD 1
CCNB CCN Bus Number 0 to 239 XXX CCNBUS 0
BAUD CCN Baud Rate 1 = 2400
2 = 4800
3 = 9600
4 =19,200
5 =38,400
X CCNBAUDD 3 = 9600