APPENDIX B — CCN TABLES (cont)
CCN CONFIGURATION TABLES (cont)
CCN SERVICE TABLES
CCN SETPOINT TABLES
TABLE DISPLAY NAME RANGE DEFAULT UNITS POINT NAME
RESETCON TEMPERATURE RESET AND DEMAND LIMIT
COOLING RESET
Cooling Reset Type N 0 CRST_TYP
4-20 MA RESET
4-20 - Degrees Reset NNN.n 10.0 deltaF MA_DEG
REMOTE RESET
Remote - No Reset Temp NNN.n 10.0 degF REM_NO
Remote - Full Reset Temp NNN.n 0.0 degF REM_FULL
Remote - Degrees Reset NNN.n 0.0 deltaF REM_DEG
RETURN TEMPERATURE RESET
Return - No Reset Temp NNN.n 10.0 deltaF RTN_NO
Return - Full Reset Temp NNN.n 0.0 deltaF RTN_FULL
Return - Degrees Reset NNN.n 0.0 deltaF RTN_DEG
DEMAND LIMIT
Demand Limit Select N 0 DMD_CTRL
Demand Limit at 20 mA NNN.n 100.0 % DMT20MA
Loadshed Group Number NN 0 SHED_NUM
Loadshed Demand Delta NN 0 % SHED_DEL
Maximum Loadshed Time NNN 60 mins SHED_TIM
Demand Limit Switch 1 NNN 80 % DLSWSP1
Demand Limit Switch 2 NNN 50 % DLSWSP2
DUALCHILL DUAL CHILLER CONFIGURATION SETTINGS
LEAD/LAG
Lead/Lag Chiller Enable Disable/Enable Disable LL_ENA
Master/Slave Select Master/Slave Master MS_SEL
Slave Address NNN 2 SLV_ADDR
Lead/Lag Balance Select N 0 LL_BAL
Lead/Lag Balance Delta NNN 168 hours LL_BAL_D
Lag Start Delay NN 5 mins LL_DELAY
Parallel Configuration No/Yes Yes PARALLEL
DISPLAY MARQUEE DISPLAY SETUP
Service Password NNNN 1111 PASSWORD
Password Enable Disable/Enable Enable PASS_EBL
Metric Display Off/On Off DISPUNIT
Language Selection N 0 LANGUAGE
TABLE DISPLAY NAME RANGE DEFAULT UNITS POINT NAME
SERVICE SERVICE
Brine Freeze Point NNN.n 34.0 degF BRN_FRZ
COMPRESSOR ENABLE
Enable Compressor A1 Disable/Enable Unit Dependent ENABLEA1
Enable Compressor A2 Disable/Enable Unit Dependent ENABLEA2
Enable Compressor A3 Disable/Enable Unit Dependent ENABLEA3
TABLE DISPLAY NAME RANGE DEFAULT UNITS POINT NAME
SETPOINT SETPOINT
COOLING
Cooling Setpoint 1 NNN.n 44.0 degF CSP1
Cooling Setpoint 2 NNN.n 44.0 degF CSP2
ICE Setpoint NNN.n 32.0 degF CSP3
RAMP LOADING
Cooling Ramp Loading N.n 1.0 CRAMP
Brine Freeze Point NNN.n 34.0 degF BRN_FRZ