Specifications

71
APPENDIX C — BACNET COMMUNICATION OPTION (cont)
Table G — Network Points List (cont)
POINT DESCRIPTION
CCN POINT
NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Dual Setpoint MODE_13 R On/Off BV:39 mode_13_1
Dual Setpoint Switch DUAL_IN R On/Off BV:29 dual_in_1
Element Comm Status R BV:2999 element_stat_1
Emergency Stop EMSTOP R/W Enabled Enabled/Emstop BV:6 emstop_1
Entering Fluid Temp EWT R °F -40-245 AV:6 ewt_1
High SCT Circuit A MODE_21 R On/Off BV:47 mode_21_1
High Temperature Cooling MODE_18 R On/Off BV:44 mode_18_1
Ice Done ICE_DONE R On/Off BV:27 ice_done_1
ICE Setpoint CSP3 R/W °F 32.0 -20-32 AV:55 csp3_1
Lead/Lag Circuit Select LEAD_TYP R/W 1 1-3 AV:43 lead_typ_1
Lead/Lag Leaving Fluid DUAL_LWT R °F -40-245 AV:32 dual_lwt_1
Leaving Fluid Temp LWT R °F -40-245 AV:7 lwt_1
Loading Sequence Select SEQ_TYPE R/W 1-2 AV:77 seq_type_1
Low Cooler Suction TempA MODE_7 R On/Off BV:35 mode_7_1
Low Sound Mode MODE_25 R On/Off BV:51 mode_25_1
Low Temperature Cooling MODE_17 R On/Off BV:43 mode_17_1
Machine Operating Hours HR_MACH R hr 0-9999 AV:57 mr_mach_1
Machine Starts CY_MACH R 0-9999 AV:58 cy_mach_1
Making ICE MODE_19 R On/Off BV:45 mode_19_1
Master/Slave control MODE_3 R On/Off BV:32 mode_3_1
Minimum Comp. On Time MODE_23 R On/Off BV:49 mode_23_1
Minimum Load Valve Relay MLV_RLY R On/Off BV:79 mlv_rly_1
Minimum OFF time active MODE_10 R On/Off BV:38 mode_10_1
Minutes Left for Start MIN_LEFT R min 00:00-15:00 AV:39 min_left_1
Minutes Off Time DELAY R/W min 0 0-15 AV:42 delay_1
Occupancy Status OCC R Yes/No BV:2008 occ_status_1
Outdoor Air Temperature OAT R/W °F -40-245 AV:1003 oa_temp_1
Override Modes in Effect MODE R Yes/No BV:5 mode_1
Percent Available Cap. CAPA_A R % 0-100 AV:12 capa_a_1
Percent Total Capacity CAP_T R % 0-100 AV:3 cap_t_1
Percent Total Capacity CAPA_T R % 0-100 AV:11 capa_t_1
Pump Off Delay Time MODE_24 R On/Off BV:50 mode_24_1
Ramp Load Limited MODE_5 R On/Off BV:33 mode_5_1
Requested Stage STAGE R 0-99 AV:9 stage_1
Saturated Condensing Tmp TMP_SCTA R °F -40-245 AV:16 tmp_scta_1
Saturated Suction Temp TMP_SSTA R °F -40-245 AV:17 tmp_ssta_1
Slow Change Override MODE_9 R On/Off BV:37 mode_9_1
Space Temperature SPT R/W °F -40-245 AV:2007 space_temp_1
Storing ICE MODE_20 R On/Off BV:46 mode_20_1
Strainer Maint. Done ST_MAINT R/W Yes/No BV:55 st_maint_1
Strainer Srvc Countdown ST_CDOWN R hr 0-9999 AV:52 st_cdown_1
Strainer Srvc Interval SI_STRNR R/W hr 0-9999 AV:51 si_strnr_1
Suction Pressure SP_A R psig 0-999 AV:14 sp_a_1
Suction Superheat Temp SH_A R °F -40-245 AV:44 sh_a_1
System Cooling Demand Level R 1-3 AV:9006 cool_demand_level_1
System Demand Limiting R ACTIVE_INACTIVE BV:83 dem_lmt_act_1
Temperature Reset MODE_14 R On/Off BV:40 mode_14_1
Timed Override in effect MODE_6 R On/Off BV:34 mode_6_1
User Defined Analog 1 R/W AV:2901 user_analog_1_1
User Defined Analog 2 R/W AV:2902 user_analog_2_1
User Defined Analog 3 R/W AV:2903 user_analog_3_1
User Defined Analog 4 R/W AV:2904 user_analog_4_1
User Defined Analog 5 R/W AV:2905 user_analog_5_1
User Defined Binary 1 R/W BV:2911 user_binary_1_1
User Defined Binary 2 R/W BV:2912 user_binary_2_1
User Defined Binary 3 R/W BV:2913 user_binary_3_1
User Defined Binary 4 R/W BV:2914 user_binary_4_1
User Defined Binary 5 R/W BV:2915 user_binary_5_1
WSM controlling Chiller MODE_2 R On/Off BV:31 mode_2_1