Specifications

CL-3
CHECK PRESSURE DROP ACROSS COOLER.
Fluid entering cooler: psig (kpa)____________
Fluid leaving cooler: psig (kpa)_______________
(psig difference) x 2.31 = ft of fluid pressure drop =____________
Plot cooler pressure drop on performance data chart (located in installation Instructions literature) to determine
total gpm (l/s).
Total gpm (l/s) =______________ Unit's rated min gpm (l/s) =___________________
Job's specified gpm (l/s) (if available):
NOTE: If unit has low fluid flow, find source of problem: check fluid piping, in-line fluid strainer, shut-off valves,
chilled water pump rotation, etc.
VISUALLY CHECK MAIN BASE BOARD FOR THE FOLLOWING:
Inspect all thermistors and transducers for possible crossed wires. Check to be sure all well-type thermistors are
fully inserted into their respective wells.
TO START THE CHILLER:
Turn the emergency on/off switch (SW2) to on position.
Turn the enable/off/remote contact switch (SW1) to the enable position.
If equipped with the optional scrolling marquee, leave the enable/off/remote contact switch (SW1) in the off
position.
NOTE: Use escape key to go up one level in the structure.
Use arrow/escape keys to illuminate run status led. Press ENTER key until 'vers' is displayed. Press ENTER key.
Record information.