Full Product Manual

United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Technical Services
Tel: 888.862.3289
www.tnb.com
G-23
Wire Joints
Wire Termination — Sta-Kon
®
Wire Termination & Insulation
High-Temperature Wire Joints
Rated for temperatures up to 150° C (302° F), 600V maximum
Molded, one-piece nylon construction for electrical insulation, UL94-V2
Brazed copper sleeve prevents separation of connection during crimping
Internal serrations enable cold flow for increased conductivity and pull-out strength
Cat. No.
PkG.
Qty.
Wire raNGe
reC.
tool
DimeNsioNs
miN. max. a B
rB4-Ht 1,000 2#18 2#16 WT2000 .36" .82"
rB44-Ht 100 2#18 2#16 WT2000 .36" .82"
rC6-Ht 500 3#16 3#14 ERG4001, WT2130A .48" .95"
rC551-Ht 100 3#16 3#14 ERG4001, WT2130A .48” .95”
rP7-Ht 500 3#14 3#12 ERG4007, WT2130A .53" 1.00"
rP12-Ht 100 3#14 3#12 ERG4007, WT2130A .53" 1.00"
Wire Joints UL Listed Combinations
Cat. No.
soliD or straNDeD aWG
rB4, rB44, rB4-10m (2) or (3) #18
(2) #16
(1) #16 and (1) or (2) #18
(3) #22
(3) #20
(3) #22 and (1) #18
(2) #22 and (3) #20
(1) or (2) #22 and (2) #18
(2) #22 and (1) #16
(3) #20 and (1) #18
(2) #20 and (1) #22
(2) #20 and (1) #16
(1) #20 and (2) #18
rC6, rC6-5m, rC55 (1) #14 with (2), (3) or (4) #16
(1) #14 with (3), (4) or (5) #18
(2) #14 with (1), (2), (3) or (4) #18
(2) #14 with (1), (2) or (3) #16
(3) #14
(4) to (7) #18
(3) #14 with (1) or (2) #18
(3) #14 with (1) #16
(1) #12 with (1), (2), (3) or (4) #18
(1) #12 with (1), (2) or (3) #16
(1) #12 with (1) or (2) #14
(5) #16
Cat. No.
soliD or straNDeD aWG
rP7, rP-12 (2) to (4) #12 AWG
(3) to (6) #14 AWG
(3) #12 and (1) #14
(2) #12 and (1) #14
(2) #12 and (2) #14
(2) #12 and (3) #14
(1) #12 and (2) #14
(1) #12 and (3) #14
(1) #12 and (4) #14
(2) #10
(1) #10 and (1) #12
(1) #10 and (1) #14
(1) #8 Str. and (1) #16
(1) #10 and (1) #16
(1) #12 and (1) #16