Full Product Manual
Table Of Contents
- Contents
- Overview
- Ring Terminals
- Flag Terminals
- Fork Terminals
- Pin Terminals
- Splice Connectors
- Wire Joints
- Heat-Shrinkable Terminals, Splices, Disconnects
- Disconnects and Male Tabs
- Luminaire Disconnects
- Ferrules
- Wire Termination Tools and Installation Kits
- Wire Termination Technical Information
- Shrink-Kon® Heat-Shrinkable Tubing
- Shrink-Kon® Splice Insulatorsand Insulating Covers
- Shrink-Kon® Installation Tools
- Shield-Kon® Shield Termination System
- Dragon-Tooth® Magnet WireTermination System
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Technical Services
Tel: 888.862.3289
www.tnb.com
G-63
Shrink-Kon
®
Heat-Shrinkable Tubing
Wire Termination — Sta-Kon
®
Wire Termination & Insulation
• Insulates and protects electrical splices and terminations
• Hig
h impact and abrasion resistance
• Thermoplastic adhesive liner
• Rated for 600V, 90° C continuous use. Continuous operating
temperature: -55° C to 110° C
• Shrink temperature of 120° C
• Meets: UL
®
486D, CSA 22.2 No. 198.2, ANSI C119.1, Western
Underground Guide Nos. 2.4, 2.5, MIL-DTL-23053/15, IEEE 383
Vertical Flame Test, ANSI C37.20.2, ICEA S-19-8 and NEMA insulation
thickness requirements
............................................................................. HSFR Series Specifications ...............................................................................
HSHR Series Heavy-Wall Heat-Shrinkable Tubing
CAT. NO.
MIN.
EXPANDED
I.D. (IN.)
MAX
RECOVERED
I.D. (IN.)
NOMINAL
RECOVERED
WALLED (IN.)
CODE CABLE
SIZE
STANDARD
LENGTH (IN.)
STD.
PKG.
QTY.
HSFR16-12-4 .35 .12 .07 #14–#10 AWG 48 25
HSFR12-6-4 .51 .16 .09 #8–#6 AWG 48 25
HSFR6-1-4 .75 .24 .09 #6–#2 AWG 48 25
HSFR4-30-4 1.10 .35 .12 #1–3/0 AWG 48 25
HSFR40-400-4 1.50 .47 .16 2/0 AWG–350 kcmil 48 25
HSFR500-1000-4 2.00 .63 .16 250–500 kcmil 48 25
Custom lengths available, subject to factory quotations.
Minimum quantities may apply.
PROPERTY
TEST
METHOD
TYPICAL
PERFORMANCE
Chemical
• Fluid Resistance
MIL-DTL-23053/5 Good to Excellent
• Copper Corrosion
ASTM D2671 No Corrosion
• Fungus Resistance
ASTM G21 No Growth
• Water Absorption
ASTM D570 0.2%
Adhesive
• Adhesive Lap Shear
(1 in./min. at 23° C)
ASTM D1002
125 psi (.875 MPa)
• Adhesive Softening Point
ASTM E28 92° C ±5° C
• Adhesive Peel Strength
(300mm/min. at 23° C)
— to steel, aluminum, P.E.
— PVC
ASTM D1000
35 pli
20 pli
• Adhesive Blocking (30° C)
ASTM D1146 No Blocking
• Adhesive Water Absorption
ASTM D570 Less than 0.3%
• Water Penetration
STM 706
No penetration after 286 hrs.
of continuous immersion
PROPERTY
TEST
METHOD
TYPICAL
PERFORMANCE
Physical
• Tensile Strength ASTM D412, ISO 37 2100 psi (14.5MPa)
• Elongation ASTM D412, ISO 37 600%
• Longitudinal Change ASTM D2671 +1%, -10%
• Specific Gravity ASTM D792 1.2
• Elongation after Heat Aging
(168 hrs. at 175° C)
ASTM D2671, ISO 37 500%
• Heat Shock
(4 hrs. at 225° C)
ASTM D2671 No cracking or flowing
• Low Temperature Flexibility
(4 hrs. at -55° C)
ASTM D2671 No cracking or splitting
• Hardness (Shore D) ASTM D2240 50D
• Oxygen Index ASTM D2863 27.00
• Flamibility ASTM D2671 Flame Retardant
Electrical
• Dielectric Strength ASTM D149 500 V/Mil (20kV/mm)
• Dielectric Voltage Withstand UL 486D No Breakdown
(2500V, 60 Hz, 1 Min.) 24kV — 1 min.,
15kV — 4 hrs.
• Volume Resistivity ASTM D257 1016 ohm-cm
3:1 Shrink Ratio
3:1 Shrink Ratio
HSFR Series — Flame-Retardant
Heavy Wall