Brochure

175
www.centuryelectricmotors.ca
Three Phase TEFC Motors
Continued from previous page
Motors specially designed, tested and warranted to
be Corona-Free for compatible inverter duty are
marked on this page with a J. See page 4 and 5
of this catalog for more Speed Engineered
®
motors
information.
Features:
Ball Bearings
Continuous Duty
Squirrel Cage
Energy Efficient $
Rigid Base
Applications:
Pumps, fans, compressors, conveyors, machine tools, designed to stand up to abusive treatment..moist, dirty, dusty and factory applications.
Full Load Service Stock Insul. Cast “C”
HP RPM Volts Amps Factor Frame Number Type Class Iron Dim. Efficiency Notes
100 3540 230/460 168.0/84.0 1.15 405TS T57016 J E+3(NP) F 37.6 94.1 362,364
100 1775 575 96.0 1.15 405T T59041 J E+3(NP) F 40.6 95.4 13,364,366
100 1775 230/460 240.0/120.0 1.15 405T T57041 J E+3(NP) F 40.6 95.4 362,364
100 1775 230/460 240.0/120.0 1.15 405TS TS18041 J E+3(NP) F 37.6 95.4 362,364
100 1180 230/460 242.0/121.0 1.15 444T T57066 J E+3(NP) F 45.7 95.0 362,364
125 3550 230/460 228.0/114.0 1.15 444TS T57017 J E+3(NP) F 44.6 95.0 8,362,364
125 1775 230/460 286.0/143.0 1.15 444T T57042 J E+3(NP) F 45.7 95.4 362,364
125 1775 230/460 286.0/143.0 1.15 444TS TS18042 J E+3(NP) F 44.6 95.4 362,364
125 1775 575 114.4 1.15 444T T59042 J E+3(NP) F 45.7 95.4 13,364,366
125 1180 230/460 300.0/150.0 1.15 445T T57067 J E+3(NP) F 47.7 95.0 362,364
150 3550 230/460 290.0/245.0 1.15 445TS T57018 J E+3(NP) F 46.6 95.0 8,362,364
150 1780 230/460 338.0/169.0 1.15 445T T57043 J E+3(NP) F 47.7 95.8 362,364
150 1780 575 135.2 1.15 445T T59043 J E+3(NP) F 47.7 95.8 13,364,366
150 1180 230/460 356.0/178.0 1.15 447T T57068 J E+3(NP) F 57.5 95.8 362,364
200 3560 230/460 228.0 1.15 447TS T57019 J E+3(NP) F 53.8 95.4 8,65,364
200 1780 460 220.0 1.15 447T T57044 J E+3(NP) F 57.5 96.2 362,364
200 1780 575 176.0 1.15 447T T59044 J E+3(NP) F 57.5 96.2 364,366
200 1185 460 234.0 1.15 449T T57069 J E+3(NP) F 57.5 95.8 362,364
Notes:
8. NEMA Design A
13. Six lead motor suitable for part winding start
65. Six lead, Wye Delta
362. 12 lead - capability for Y Start-Delta Run
364. Open bearings with regreasing provisions
366. 6 leads
Standard, EPAct CC001A
(E-Plus
®
motors) and Premium
(E-Plus
®
3 motors) Efficiency
40°C Ambient
60 Hz
TEFC
E-Plus
®
Motors meet the require-
ments of the Energy Policy Act of
1992. E-Plus
®
3 motors exceed the
requirements of the Energy Policy
Act of 1992. E+3(NP) is NEMA
Premium Efficient.
T57016