User's Manual

8
32A/40A 48A 80A
L1 (Black) 8 AWG 6 AWG 3 AWG
L2 (Red) 8 AWG 6 AWG 3 AWG
Ground
(Green)
8 AWG (THHN) 8 AWG (THHN) 6 AWG (THHN)
6. Turn on the circuit breaker that supplies power to the NEMA 14-50 outlet, NEMA 6-50
outlet, or hardwired electrical connection.
Load Balancing
> Load balance to Circuit only.
> Load balance to panel is NOT recommended.
NOTE
Balancing to the panel or location can be done on a system that would otherwise
work safely on its own. This can reduce usage during peak hours, saving cost to both
the user and the owner of the stations.
> Can only balance stations with the same specications.
> Balancing specications cannot exceed the rated continuous load of the circuit. (50
amp circuit = 40 amp continuous load allowed) (NEC 625.41 & 42) 2017 code.
> Per NEC 625.42 additional outlets per circuit can be added due to the JuiceNet Automated
Load Management System.
> Recommend no more than 3 per circuit. The maximum number of stations per circuit is
determined by dividing the number of continuous load amps allowed based on circuit
size by 8. (e.g. 40 amps / 8 amps = 5 stations maximum). Note this may result in a slower
charge per car.