PROBLEM: Water discharges from anti-siphon cap.
CAUSE: Heads are above valve.
SOLUTION: Raise valve or use angle valve.
CAUSE: Anti-siphon float is missing or damaged.
SOLUTION: Check or replace float.
PROBLEM: Valve does not close completely.
CAUSE: Static pressure is above 125 PSI.
SOLUTION: Install a mainline pressure regulator.
PROBLEM: Valve does not open.
CAUSE: Actuator ports are blocked.
SOLUTION: Shut off water supply, remove solenoid and solenoid
adapter, open water supply momentarily and flush out solenoid
ports. Reinstall solenoid. Open water supply and test manually.