ATS Installation Manual

RELIANCE CONTROLS ARL SERIES AUTOMATIC TRANSFER SWITCH
CONTROLS AND FEATURES
14
Select ARL Circuits - Generator
Select the circuits to be powered by the generator. Remove the
selected breakers from the main panel.
If the removed breakers are of an accepting type, install them
in the ARL. If not,discard them and buy suitable breakers of the
correct ampacity.
Extend the branch circuit conductors from the main panel into
the ARL by using suitable gauge and color of approved building
wire and appropriate wire connectors.
The ARL is UL listed for several 1-inch interchangeable breakers
(see label on the inside cover of the ARL) or, page 10, of the
Circuit Breakers section.
Install only circuit breakers that are compatible with ARL branch
circuit.
Pull wire to new circuit breakers in ARL branch circuit from
circuit breaker in Load center.
Use Copper Wire only, 75°C Minimum
Connect each branch circuit conductor (wire) to its appropriate
branch circuit breaker from the Load center.
Repeat for each of the selected circuits.
The branch conductors must be connected to the same
ampacity breakers as they were when they were in the Load
center.
Make certain that the total amp capacity of the selected circuits
does not exceed the maximum capacity of the generator.
Balance the load on the ARL by dividing the branch circuit
breakers evenly between the two sides as shown in Figure 1.
Figure 1 – ARL Branch Circuit Breaker
15
20
Load Center Circuit Breakers