Full Product Manual

100565 - 2000W PORTABLE INVERTER GENERATOR
STORAGE
25
6. When gasoline stops flowing from the clear tube, rotate
drain screw clockwise until tight. Properly dispose of
the drained gasoline according to local regulations or
guidelines.
7. Turn the EZ Start dial to the STOP position.
8. Follow steps 8-12 according to Short Term Storage.
Removing from Storage
If the generator has been improperly stored for a long period
of time with gasoline in the gasoline tank and/or carburetor, all
fuel must be drained and the carburetor must be thoroughly
cleaned. This process involves technically advanced tasks.
For assistance please call our Technical Support Team at
1-877-338-0999.
If the gasoline tank and carburetor were properly emptied of all
gasoline prior to the generator being stored, follow the below
steps when removing from storage.
1. Be sure the EZ Start dial is in the STOP position.
2. Add gasoline to the generator according to Add Fuel:
Gasoline.
3. Move the EZ Start dial to the START position.
4. After 5 minutes check the carburetor and air filter areas for
any leaking gasoline. If any leaks are found, the carburetor
will need to be disassembled and cleaned or replaced. If
no gasoline leaks are found, turn the EZ Start dial to the
“STOPposition.
5. Check engine oil level and add clean, fresh oil if needed.
See Oil Specifications for proper oil type.
6. Check and clear air filter of any obstructions such as bugs
or cobwebs. If necessary, clean air filter according to
Cleaning the Air Filter.
7. Start the generator according to Starting the Engine.
! DANGER
Generator exhaust contains odorless and colorless carbon
monoxide gas.
To avoid accidental or unintended ignition of your generator
during periods of storage, the following precautions should
be followed:
When storing the generator make sure the EZ Start dial
is set to the “OFF” position.