Instructions / Assembly

200960 - 2000W DUAL FUEL INVERTER GENERATOR
OPERATION
20
NOTICE
For gasoline starting in standard ambient temperature
>59°F (15°C): Keep EZ Start dial in “CHOKE” position for three
pulls of the recoil cord. If generator does not start after three
pulls, rotate the EZ Start dial to the “RUN” position for the next
three pulls. Too much choke leads to spark plug fouling and
engine flooding. This will cause the engine not to start.
NOTICE
For gasoline starting in cold ambient temperature < 59°F
(15°C): Keep the EZ Start dial in the “CHOKE” position until
engine starts. As soon as the engine starts and runs smoothly
turn the EZ Start dial to the “RUN” position. In extreme cold
temperatures, this may take several seconds.
NOTICE
If the engine starts but does not continue to run make certain
that the generator is on a flat, level surface. The engine is
equipped with a low oil sensor that will prevent the engine
from running when the oil level falls below a critical threshold.
Starting the Engine: Propane (LPG)
1. Make certain the generator is on a flat, level surface.
2. Disconnect all electrical loads from the generator. Never start
or stop the generator with electrical devices plugged in or
turned on.
3. Open the fuel valve on the propane cylinder.
Cold Engine Start
4. Move the EZ Start dial to the “CHOKE” position.
5. Slowly pull the starter cord 3-5 times to prime the engine.