GENERAL INFORMATION
Scope:
This specication covers Copper Tube Size (CTS) CPVC manufactured to standard dimensional ratio (SDR) 11 for
non-potable water distribution. This system is intended for pressure applications where the operating temperature will
not exceed 180° F at 100 psi.
Specication:
Pipe shall be manufactured from virgin rigid CPVC (chlorinated polyvinyl chloride) vinyl compounds with a cell class
of 24448 as identied in ASTM D 1784. Fittings shall be manufactured from virgin rigid CPVC (chlorinated polyvinyl
chloride) vinyl compounds with a cell class of 23447 as identied in ASTM D 1784.
ReUze CTS CPVC pipe and ttings shall conform to ASTM D 2846. Pipe and ttings shall be manufactured as a
system and be the product of one manufacturer. All pipe and ttings shall be manufactured in the United States.
Pipe and ttings shall conform to NSF International Standard 14. The pipe shall be listed by NSF International for
reclaimed water and bear the mark “NSF-rw.”
Installation:
Installation shall comply with the latest installation instructions published by Charlotte Pipe and Foundry and shall
conform to all applicable plumbing, re, and building code requirements. Buried pipe shall be installed in accordance
with ASTM F 1668 and ASTM D 2774. Solvent cement joints shall be made using CPVC cement conforming to ASTM
F 493. If a primer is required by local plumbing or building codes, then a primer conforming to ASTM F 656 should
be used. The system shall be protected from chemical agents, re-stopping materials, thread sealant, plasticized-
vinyl products or other aggressive chemical agents not compatible with CPVC compounds. The system shall be
hydrostatically tested after installation WARNING! Never test with or transport/store compressed air or gas in CPVC
pipe or ttings. Doing so can result in explosive failures and cause severe injury or death.
Referenced Standards:
ASTM D 1784: Rigid Vinyl Compounds
ASTM D 2774 Underground Installation of Thermoplastic Pressure Piping
ASTM D 2846: CPVC Plastic Hot and Cold Water Distribution System
ASTM F 493: Solvent Cements for CPVC Pipe and Fittings
ASTM F 1668: Procedures for Buried Plastic Pipe
NSF Standard 14: Plastic Piping Components & Related Materials
SUBMITTAL FOR CHARLOTTE PIPE
®
REUZE
®
CPVC COPPER
TUBE SIZE (CTS) NON-POTABLE WATER DISTRIBUTION SYSTEM
Charlotte Pipe, ReUze and Charlotte Pipe and Foundry Company are registered trademarks of Charlotte Pipe and Foundry Company.
FO-SUB-CPVC-REUZE (11-10-17)
Date: ________________
Job Name: ______________________________ Location: _______________________________
Engineer: _______________________________ Contractor: ______________________________
Not all tting patterns shown
Bushing
Cap
Street Quarter
Bend
Eighth Bend
Quarter Bend
Male Adapter
Charlotte Pipe and Foundry Company • P.O. Box 35430 Charlotte, NC 28235 • (800) 438-6091 • www.charlottepipe.com
Tee Coupling
Sizes Available
Product
1
⁄
2
3
⁄
4
1
1
1
⁄
4
1
1
⁄
2
2
ReUze
®
CPVC CTS SDR 11
• • • • •
PIPE REFERENCE GUIDE
Brass Male Adapter
1
⁄2
0.382 (9.70) 0.183 (4.65) 0.102 (2.59)
3
⁄4
0.507 (12.88) 0.235 (5.97) 0.102 (2.59)
1 0.633 (16.08) 0.287 (7.29) 0.102 (2.59)
1
1
⁄4
0.758 (19.25) 0.339 (8.61) 0.102 (2.59)
1
1
⁄2
0.884 (22.45) 0.391 (9.93) 0.102 (2.59)
2 1.134 (28.83) 0.495 (12.57) 0.102 (2.59)
NOMINAL “G” MINIMUM “J” MINIMUM “N” MINIMUM
SIZE (IN.) IN. (mm) IN. (mm) IN. (mm)
MINIMUM DIMENSIONS FROM CENTER TO END OF SOCKET
(LAYING LENGTH) FOR CPVC 41, SDR 11 FITTINGS
M
A
D
E
I
N
U
.
S
.
A
.