5.2.28. DITHER (Engine handshake)
This menu item allows enabling/disabling of engine handshake. When enabled, the TPG will vary the engine speed
+/- 5 RPM around the desired engine speed. Some engines may require consistent RPM modification in order to
maintain remote RPM control.
The display will show DITHER=X. Use the INC and DEC switches to select Y or N.
Range = Y (enabled) or N (disabled). [default = N]
5.2.29. LAG PSI (Pressure lag)
This menu item allows configuration of the pressure lag which defines the maximum allowable difference that the
actual pressure is behind the commanded set-point before a “wait” (catch up) state is introduced while operating in
pressure mode.
The display will show LAG (PSI)=X. Use the INC and DEC switches to adjust the pressure lag value.
Range = 1 PSI to 20 PSI (in 1 PSI steps). [default = 5 PSI]
5.2.30. PUMP HOURS
This menu item allows setting/resetting of the total pump hours.
The display will show PUMP X.Xh. Use the INC and DEC switches to adjust the pump hours.
Range = 0.0 to 999.9 hours (in 0.1 hour steps). [default = 0]
5.2.31. BCM1 VER (Body Control Message 1 version)
This menu item allows configuration of the message configuration version transmitted in the Scania
Body Control Message 1.
The display will show BCM1 VER: X. Use the INC and DEC switches to adjust the value.
Range = 0 to 255. [default = 1]
5.2.32. SCANIA MODE? (Scania governor type)
This menu item allows configuration of the Scania requested governor type in the Body Control Message 1.
The display will show MODE: XXXXXX. Use the INC and DEC switches to adjust the value.
Range = NORMAL or STIFF. [default = NORMAL]
5.2.33. IDLE STEPS (Analog control idle)
This menu item allows the configuration of the analog control signal idle voltage.
The display will show IdleSteps:XX. Use the INC and DEC switches to adjust the value.
Range = 0 to 60 [default = 32]
5.2.34. OKAY2PUMP (Okay to pump interlock source)
This menu item allows the configuration of the “okay to pump” interlock source.
NORM The OKAY TO PUMP text only illuminates when the throttle ready and pump engaged interlocks are
active.
PIN4 The OKAY TO PUMP text only illuminates when pin 4 of the 12-pin Deutsch connector has power
applied.
The display will show OK2PUMP=X. Use the INC and DEC switches to adjust the value.
Range = NORM or PIN4 [default = NORM]