Programming the EFC is simply a matter of selecting items from a menu.
To enter the programming menu, Press and hold the MODE and MENU switches at the
same time until Press Idle to Exit is displayed on the information center, then release both
switches.
Moving through the menu is accomplished by pressing the MENU switch.
Change to a selection is performed by using the INC and DEC switches.
Exiting the programming menu is done in one of two ways.
Pressing IDLE will exit the menu and save changes.
Pressing MODE will exit the menu without saving changes.
Programming Menu Options:
RPM Preset Point: (preset engine speed)
Pressure Set (PSI): (preset PSI)
Engine Hourmeter: (information only)
Pump Hourmeter: (information only)
Engine Degrees: (oil or coolant)
Pump Pressure (PSI): (pressure reading if active)
DDEC Software Ver: (ECU revision level)
EFC Software Ver: (EFC revision level)
Fire Commander I/O Test: (test switches)
Press [MODE] Test Lights: (tests display panel)
Set Time Clock: (set clock)
Units of Measure: (English/Metric)
Welcome Message: (enable/disable)
Codes Currently Active: (information)
Connector Data: (displays connection info.)
SAVE? [Idle=Y] [Mode=N] (exit and save options)
Use the MENU switch to scroll through the menu.
Use the INC and DEC switches when the item you want to change is displayed.
When changes are complete, press IDLE to exit and save changes.
To exit the menu without saving changes, press MODE.
Programming the Detroit Diesel Electronic Fire Commander: