BALANCING THE UNIT
IO-VENT-NC WWW.CLEANCOMFORT.COM

TOOLS REQUIRED TO
BALANCE THE HRV/ERV
A Magnehelic gauge capable of
measuring 0 to 2.0 inch of water
(0 to 500 Pa) and two (2) plastic
hoses.
• A balancing reference chart
located on the HRV/ERV access
door panel.
CONSIDERATION WHEN
BALANCING THE HRV/ERV
Seal all the unit ductwork with
tape. Close all windows and
doors.
Insure all exhaust devices such as
range hood, dryer and bathroom
fans are OFF.
Make sure that all lters are
clean and that there is no
obstruction in ductwork
Make sure that the forced air
system blower is “ON” when
connected to an existing forced
air system ductwork.
If it is a direct duct system
installation ensure forced air
system blower is “OFF”.
USING THE DUOTROL
SELECTOR SWITCH
When on Balancing Mode, the
Selector Switch allows you to
choose the motor you want to set.
GREEN LIGHT
Mode Selector
A) Closed Duotrol Cover
1. INTER (Exhaust Motor)
2. CONT (Both Motors)
3. OFF (Supply Motor)
YELLOW LIGHT
Balancing Mode
B) Open Duotrol Cover
1. UP (Exhaust Motor)
2. MIDDLE (Both Motors)
3. DOWN (Supply Motor)
IMPORTANT: Insure the HRV/ERV
has completed the defrost sequence.
That the dehumidistat is deactivated
by turning the round dial to the “OFF
position, the Range is” NORMAL”, the
mode is “CONT” and the Cycle per
Hour is set at “0/0”.
NOTE: The unit is considered
balanced even if there is a dierence
of ±10 cfm (or ± 5 l/s or 17 m³/h)
between the two air ows
DUOTROL™ BALANCING SYSTEM PROCEDURES
Step 1: Place the Magnehelic gauge on a level
surface and adjust the needle to zero.
Step 2: Connect the two (2) plastic hoses to the
gauge on the HIGH & LOW pressure connections.
Step 3: Once the total ventilation requirements are
determined, you can start balancing the HRV/ERV.
(Refer to 1. Ventilation Requirements)
Step 4: Remove the (4) four nylon knock out seals
located on the HRV/ERV access door. (Ref g 11.1)
Fig 11.1
Fresh Air
from Outside
Stale Air
to Outside
Stale Air
from Home
Fresh
Air
Stale
Air
Fresh Air
to Home
Remove all four (4)
nylon knock out seals.
Do not discard.
LOWLOW
LOW
LOW
HIGH
HIGH
HIGH
HIGH
Aspiration
d'air frais
Évacuation
d'air vicié
Aspiration
d'air vicié
Air frais
Air vicié
Distribution
d'air frais
BASBAS
BAS
BAS
HAUT
HAUT
HAUT
HAUT
Enlever les quatre (4)
bouchons de nylon.
Ne pas les jeter.
Pressure / Pression Fresh air / Air frais Stale air / Air vicié
IN. W.G. Pascal CFM
L/s
CFM
L/s
PO. d’eau (Pa) PCM PCM
0.36 90 216 102 - -
0.34 85 209 99 222 105
0.32 80 200 94 214 101
0.30 75 192 91 207 98
0.28 70 183 86 198 93
0.26 65 173 82 189 89
0.24 60 163 77 180 85
0.22 55 153 72 170 80
0.20 50 142 67 159 75
0.18 45 131 62 148 70
0.16 40 119 56 136 64
0.14 35 107 50 124 59
0.12 30 95 45 111 52
0.10 25 82 39 97 46
0.08 20 68 32 83 39
0.06 15 55 26 69 33
0.04 10 55 26 54 25
Balancing chart 2.0Balancing chart 1.5
Pressure / Pression Fresh air / Air frais Stale air / Air vicié
IN. W.G. Pascal CFM
L/s
CFM
L/s
PO. d’eau (Pa) PCM PCM
0.60 149 186 88 187 88
0.58 144 182 86 184 87
0.56 139 177 84 180 85
0.54 135 172 81 176 83
0.52 130 167 79 173 82
0.50 125 162 76 169 80
0.48 120 157 74 165 78
0.46 115 152 72 161 76
0.44 110 146 69 156 74
0.42 105 141 67 152 72
0.40 100 136 64 147 69
0.38 95 130 61 143 67
0.36 90 125 59 138 65
0.34 85 119 56 133 63
0.32 80 113 53 128 60
0.30 75 107 50 123 58
0.28 70 102 48 117 55
0.26 65 96 45 112 53
0.24 60 90 42 106 50
0.22 55 84 40 100 47
0.20 50 78 37 94 44
0.18 45 71 34 88 42
0.16 40 65 31 82 39
0.14 35 59 28 76 36
0.12 30 52 25 69 33
0.10 25 46 22 62 29
0.08 20 39 18 56 26
0.06 15 33 16 49 23
Step 5: Connect the two (2) plastic hoses from the
gauge to the HIGH & LOW balancing pressure taps
on the fresh or stale air side located on the HRV/
ERV access door (Ref Fig 11.2)
Fig 11.2
Fresh Air
from Outside
Stale Air
to Outside
Stale Air
from Home
Fresh
Air
Stale
Air
Fresh Air
to Home
Remove all four (4)
nylon knock out seals.
Do not discard.
LOWLOW
LOW
LOW
HIGH
HIGH
HIGH
HIGH
Aspiration
d'air frais
Évacuation
d'air vicié
Aspiration
d'air vicié
Air frais
Air vicié
Distribution
d'air frais
BASBAS
BAS
BAS
HAUT
HAUT
HAUT
HAUT
Enlever les quatre (4)
bouchons de nylon.
Ne pas les jeter.
Pressure / Pression Fresh air / Air frais Stale air / Air vicié
IN. W.G. Pascal CFM
L/s
CFM
L/s
PO. d’eau (Pa) PCM PCM
0.36 90 216 102 - -
0.34 85 209 99 222 105
0.32 80 200 94 214 101
0.30 75 192 91 207 98
0.28 70 183 86 198 93
0.26 65 173 82 189 89
0.24 60 163 77 180 85
0.22 55 153 72 170 80
0.20 50 142 67 159 75
0.18 45 131 62 148 70
0.16 40 119 56 136 64
0.14 35 107 50 124 59
0.12 30 95 45 111 52
0.10 25 82 39 97 46
0.08 20 68 32 83 39
0.06 15 55 26 69 33
0.04 10 55 26 54 25
Balancing chart 2.0Balancing chart 1.5
Pressure / Pression Fresh air / Air frais Stale air / Air vicié
IN. W.G. Pascal CFM
L/s
CFM
L/s
PO. d’eau (Pa) PCM PCM
0.60 149 186 88 187 88
0.58 144 182 86 184 87
0.56 139 177 84 180 85
0.54 135 172 81 176 83
0.52 130 167 79 173 82
0.50 125 162 76 169 80
0.48 120 157 74 165 78
0.46 115 152 72 161 76
0.44 110 146 69 156 74
0.42 105 141 67 152 72
0.40 100 136 64 147 69
0.38 95 130 61 143 67
0.36 90 125 59 138 65
0.34 85 119 56 133 63
0.32 80 113 53 128 60
0.30 75 107 50 123 58
0.28 70 102 48 117 55
0.26 65 96 45 112 53
0.24 60 90 42 106 50
0.22 55 84 40 100 47
0.20 50 78 37 94 44
0.18 45 71 34 88 42
0.16 40 65 31 82 39
0.14 35 59 28 76 36
0.12 30 52 25 69 33
0.10 25 46 22 62 29
0.08 20 39 18 56 26
0.06 15 33 16 49 23
Note: If the gauge needle drops below zero,
reverse the plastic hose connections.
Step 6: Press the (+) and (–) buttons on the
Duotrol™ simultaneously until you see the yellow
light. Once the indicator light turns yellow and the
unit goes to high speed you are in balancing mode.
When in balancing mode the selector switch on
the Duotrol™ becomes the motor selector switch.
INTER (Right Motor = Stale Airow), CONT (Both
Motors) and OFF (Left Motor = Fresh Airow)
Step 7: To adjust the (fresh air), select the «OFF»
position on the Duotrol™. Ensure the plastic hoses
from the gauge are connected to the HIGH & LOW
balancing pressure taps on the fresh airow side
located on the HRV/ERV access door. (Ref Fig 11.2).
To adjust the airow rates, press the (–) button to
decrease or press the (+) button to increase the
airow rates until you reach the calculated fresh
airow requirements.
Step 8: To adjust the (stale air) select the «INTER»
position on the Duotrol™. Ensure the plastic hoses
from the gauge are connected to the HIGH &
LOW balancing pressure taps on the stale air side
located on the HRV/ERV access door. (Ref Fig 11.2)
To adjust the airow rates, press the (–) button to
decrease or press the (+) button to increase the
airow rates until you reach the calculated stale
airow requirements.
Step 9: Once this is completed, you have balanced
the airow rates of your HRV/ERV. To exit the
balancing mode you must press (+) and (–) buttons
on the Duotrol™ simultaneously until solid green
LED appears then release. The indicator light will
turn green to indicate normal operation mode.
Seal the (4) four balancing pressure taps with the
nylon knock out seals removed in Step 4.
Step 10: Mark down the balanced air ow rates
information on a label including in the kit. Apply
the label to the HRV/ERV access door for future
reference (e.g. date, balance airow rate, your
name, phone number and business address).
Note: Once the HRV/ERV is balanced, switch
to «CONT» on the Duotrol™ By using (+) and (–)
buttons you can set the continuous speed.
For Balancing Charts,
- Refer to page 22 of this manual