VE Series Installation Manual

(Reference:
BALANCING THE UNIT

WWW.CLEANCOMFORT.COM IO-VENT-NC
TOOLS REQUIRED TO
BALANCE THE HRV/ERV
A Magnehelic gauge capable of
measuring 0 to 2.0 inch of water
(0 to 500 Pa) and two (2)
plastic hoses.
• A balancing reference chart
located on the HRV/ERV access
door panel.
CONSIDERATION WHEN
BALANCING THE HRV/ERV
Seal all the unit ductwork with tape.
Close all windows and doors.
Insure all exhaust devices such as
range hood, dryer and bathroom
fans are o.
• That the integrated balancing
dampers located in the collars are
fully open.(Fresh Air damper ref Fig.
11.5, Stale Air damper ref Fig. 11.6)
Make sure that all lters are
clean and that there is no
obstruction in ductwork
Make sure that the forced air
system blower is “ON” when
connected to an existing forced
air system ductwork.
If it is a direct duct system
installation ensure forced air
system blower is “OFF”.
IMPORTANT: Insure the HRV/
ERV has completed the defrost
sequence. That the dehumidistat
is deactivated by turning the
round dial to the “OFF” position,
the Range is” NORMAL”, the mode
is “CONT” and the Cycle per Hour
is set at “0/0”.
NOTE: The unit is considered
balanced even if there is a
dierence of ±10 cfm (or ± 5 l/s or
17 m³/h) between the two air ows
Note to installer: For installation
purposes, the VH30100RNC &
VH30140RNC are designed with
pre-determined airow speed
values that are stored in memory.
The VH30100RNC & VH30140RNC
platform are designed and can
be equipped with the Duotrol
speed & balancing control system
kit. This factory option must be
present to control the motors
independently, when more
accurate airow settings are
required or for testing purposes.
Please contact 1-888-724-5211 for
further instructions/information
on this process.
BALANCING PROCEDURES WITH INTEGRATED BALCANCING DAMPERS
Step 1: Place the Magnehelic gauge on a level
surface and adjust the needle to zero.
Step 2: Connect the two (2) plastic hoses to the
gauge on the HIGH & LOW pressure connections.
Step 3: Once the total ventilation requirements are
determined, you can start balancing the HRV/ERV.
(Refer to 1. Ventilation Requirements)
Step 4: Remove the four (4) nylon knock out seals
located on the HRV/ERV access door. (Ref Fig 11.3)
Fig 11.3
Fresh
Air
Stale
Air
Remove all four (4)
nylon knock out seals.
Do not discard.
Damper
Lever
Front
Stale
Air
HIGHHIGH HIGHHIGH
LOW
LOW LOWLOW
Damper
Lever
Front
Fresh
Air
Air Vicié Air frais
Enlever les quatre
(4) bouchons
à défoncer de nylon.
Ne pas les jeter.
HAUTHAUT
BAS
BAS
HAUT
HAUT
BAS
BAS
Levier
du registre
Devant
Air
vicié
Levier
du registre
Devant
Air
frais
Pressure / Pression Fresh air / Air frais Stale air / Air vicié
IN. W.G. Pascal CFM
L/s
CFM
L/s
PO. d’eau (Pa) PCM PCM
0.50 125 - - 161 76
0.53 132 - - 159 75
0.56 139 - - 156 74
0.59 147 - - 153 72
0.62 154 - - 149 70
0.65 162 - - 146 69
0.68 169 - - 142 67
0.71 177 - - 138 65
0.74 184 149 70 133 63
0.77 192 147 69 129 61
0.80 199 144 68 124 59
0.83 207 141 67 119 56
0.86 214 138 65 114 54
0.89 222 133 63 109 51
0.92 229 128 60 103 49
0.95 237 123 58 97 46
0.98 244 116 55 91 43
1.01 252 109 51 85 40
1.04 259 101 48 78 37
1.07 267 93 44 71 34
1.10 274 84 40 64 30
1.13 281 74 35 57 27
1.16 289 64 30 50 24
1.19 296 53 25 42 20
1.22 304 41 19 34 16
1.25 311 29 14 26 12
Step 5: Connect the two (2) plastic hoses from the
gauge to the HIGH & LOW balancing pressure taps
on the fresh or stale air side located on the HRV/
ERV access door (Ref Fig 11.4)
Fig 11.4
Fresh
Air
Stale
Air
Remove all four (4)
nylon knock out seals.
Do not discard.
Damper
Lever
Front
Stale
Air
HIGHHIGH HIGHHIGH
LOW
LOW LOWLOW
Damper
Lever
Front
Fresh
Air
Air Vicié Air frais
Enlever les quatre
(4) bouchons
à défoncer de nylon.
Ne pas les jeter.
HAUTHAUT
BAS
BAS
HAUT
HAUT
BAS
BAS
Levier
du registre
Devant
Air
vicié
Levier
du registre
Devant
Air
frais
Pressure / Pression Fresh air / Air frais Stale air / Air vicié
IN. W.G. Pascal CFM
L/s
CFM
L/s
PO. d’eau (Pa) PCM PCM
0.50 125 - - 161 76
0.53 132 - - 159 75
0.56 139 - - 156 74
0.59 147 - - 153 72
0.62 154 - - 149 70
0.65 162 - - 146 69
0.68 169 - - 142 67
0.71 177 - - 138 65
0.74 184 149 70 133 63
0.77 192 147 69 129 61
0.80 199 144 68 124 59
0.83 207 141 67 119 56
0.86 214 138 65 114 54
0.89 222 133 63 109 51
0.92 229 128 60 103 49
0.95 237 123 58 97 46
0.98 244 116 55 91 43
1.01 252 109 51 85 40
1.04 259 101 48 78 37
1.07 267 93 44 71 34
1.10 274 84 40 64 30
1.13 281 74 35 57 27
1.16 289 64 30 50 24
1.19 296 53 25 42 20
1.22 304 41 19 34 16
1.25 311 29 14 26 12
Step 6: Set the unit on high speed by connecting
the Vectra EHC-1.0 controller to the HRV/ERV,
power “ON” and select the 20MIN/HR operating
mode by pressing the “PREF” button on the Vectra
EHC 1.0 control.
ATTENTION: If there is no control present on the RNC
1.0, will automatically run on a continuous high speed
operating mode.
Step 7: To adjust the (fresh air), ensure the plastic
hoses from the gauge are connected to the HIGH &
LOW balancing pressure taps on the fresh air side
located on the HRV/ERV access door. (Ref Fig 11.4).
Adjust the fresh airow integrated balancing damper
lever counterclockwise until you reach the calculated
fresh airow requirements. (Ref Fig 11.5).
Fig 11.5
Fresh
Air
Stale
Air
Remove all four (4)
nylon knock out seals.
Do not discard.
Damper
Lever
Front
Stale
Air
HIGHHIGH HIGHHIGH
LOW
LOW LOWLOW
Damper
Lever
Front
Fresh
Air
Air Vicié Air frais
Enlever les quatre
(4) bouchons
à défoncer de nylon.
Ne pas les jeter.
HAUTHAUT
BAS
BAS
HAUT
HAUT
BAS
BAS
Levier
du registre
Devant
Air
vicié
Levier
du registre
Devant
Air
frais
Pressure / Pression Fresh air / Air frais Stale air / Air vicié
IN. W.G. Pascal CFM
L/s
CFM
L/s
PO. d’eau (Pa) PCM PCM
0.50 125 - - 161 76
0.53 132 - - 159 75
0.56 139 - - 156 74
0.59 147 - - 153 72
0.62 154 - - 149 70
0.65 162 - - 146 69
0.68 169 - - 142 67
0.71 177 - - 138 65
0.74 184 149 70 133 63
0.77 192 147 69 129 61
0.80 199 144 68 124 59
0.83 207 141 67 119 56
0.86 214 138 65 114 54
0.89 222 133 63 109 51
0.92 229 128 60 103 49
0.95 237 123 58 97 46
0.98 244 116 55 91 43
1.01 252 109 51 85 40
1.04 259 101 48 78 37
1.07 267 93 44 71 34
1.10 274 84 40 64 30
1.13 281 74 35 57 27
1.16 289 64 30 50 24
1.19 296 53 25 42 20
1.22 304 41 19 34 16
1.25 311 29 14 26 12
Fresh
Air
Stale
Air
Remove all four (4)
nylon knock out seals.
Do not discard.
Damper
Lever
Front
Stale
Air
HIGHHIGH HIGHHIGH
LOW
LOW LOWLOW
Damper
Lever
Front
Fresh
Air
Air Vicié Air frais
Enlever les quatre
(4) bouchons
à défoncer de nylon.
Ne pas les jeter.
HAUTHAUT
BAS
BAS
HAUT
HAUT
BAS
BAS
Levier
du registre
Devant
Air
vicié
Levier
du registre
Devant
Air
frais
Pressure / Pression Fresh air / Air frais Stale air / Air vicié
IN. W.G. Pascal CFM
L/s
CFM
L/s
PO. d’eau (Pa) PCM PCM
0.50 125 - - 161 76
0.53 132 - - 159 75
0.56 139 - - 156 74
0.59 147 - - 153 72
0.62 154 - - 149 70
0.65 162 - - 146 69
0.68 169 - - 142 67
0.71 177 - - 138 65
0.74 184 149 70 133 63
0.77 192 147 69 129 61
0.80 199 144 68 124 59
0.83 207 141 67 119 56
0.86 214 138 65 114 54
0.89 222 133 63 109 51
0.92 229 128 60 103 49
0.95 237 123 58 97 46
0.98 244 116 55 91 43
1.01 252 109 51 85 40
1.04 259 101 48 78 37
1.07 267 93 44 71 34
1.10 274 84 40 64 30
1.13 281 74 35 57 27
1.16 289 64 30 50 24
1.19 296 53 25 42 20
1.22 304 41 19 34 16
1.25 311 29 14 26 12
Step 8: To adjust the (stale air), ensure the plastic
hoses from the gauge are connected to the HIGH
& LOW balancing pressure taps on the stale air
side located on the HRV/ERV access door. (Ref Fig
11.4). Adjust the stale airow integrated balancing
damper lever until you reach the calculated stale
airow requirements. (Ref Fig 11.6).
Fig 11.6
Fresh
Air
Stale
Air
Remove all four (4)
nylon knock out seals.
Do not discard.
Damper
Lever
Front
Stale
Air
HIGHHIGH HIGHHIGH
LOW
LOW LOWLOW
Damper
Lever
Front
Fresh
Air
Air Vicié Air frais
Enlever les quatre
(4) bouchons
à défoncer de nylon.
Ne pas les jeter.
HAUTHAUT
BAS
BAS
HAUT
HAUT
BAS
BAS
Levier
du registre
Devant
Air
vicié
Levier
du registre
Devant
Air
frais
Pressure / Pression Fresh air / Air frais Stale air / Air vicié
IN. W.G. Pascal CFM
L/s
CFM
L/s
PO. d’eau (Pa) PCM PCM
0.50 125 - - 161 76
0.53 132 - - 159 75
0.56 139 - - 156 74
0.59 147 - - 153 72
0.62 154 - - 149 70
0.65 162 - - 146 69
0.68 169 - - 142 67
0.71 177 - - 138 65
0.74 184 149 70 133 63
0.77 192 147 69 129 61
0.80 199 144 68 124 59
0.83 207 141 67 119 56
0.86 214 138 65 114 54
0.89 222 133 63 109 51
0.92 229 128 60 103 49
0.95 237 123 58 97 46
0.98 244 116 55 91 43
1.01 252 109 51 85 40
1.04 259 101 48 78 37
1.07 267 93 44 71 34
1.10 274 84 40 64 30
1.13 281 74 35 57 27
1.16 289 64 30 50 24
1.19 296 53 25 42 20
1.22 304 41 19 34 16
1.25 311 29 14 26 12
Fresh
Air
Stale
Air
Remove all four (4)
nylon knock out seals.
Do not discard.
Damper
Lever
Front
Stale
Air
HIGHHIGH HIGHHIGH
LOW
LOW LOWLOW
Damper
Lever
Front
Fresh
Air
Air Vicié Air frais
Enlever les quatre
(4) bouchons
à défoncer de nylon.
Ne pas les jeter.
HAUTHAUT
BAS
BAS
HAUT
HAUT
BAS
BAS
Levier
du registre
Devant
Air
vicié
Levier
du registre
Devant
Air
frais
Pressure / Pression Fresh air / Air frais Stale air / Air vicié
IN. W.G. Pascal CFM
L/s
CFM
L/s
PO. d’eau (Pa) PCM PCM
0.50 125 - - 161 76
0.53 132 - - 159 75
0.56 139 - - 156 74
0.59 147 - - 153 72
0.62 154 - - 149 70
0.65 162 - - 146 69
0.68 169 - - 142 67
0.71 177 - - 138 65
0.74 184 149 70 133 63
0.77 192 147 69 129 61
0.80 199 144 68 124 59
0.83 207 141 67 119 56
0.86 214 138 65 114 54
0.89 222 133 63 109 51
0.92 229 128 60 103 49
0.95 237 123 58 97 46
0.98 244 116 55 91 43
1.01 252 109 51 85 40
1.04 259 101 48 78 37
1.07 267 93 44 71 34
1.10 274 84 40 64 30
1.13 281 74 35 57 27
1.16 289 64 30 50 24
1.19 296 53 25 42 20
1.22 304 41 19 34 16
1.25 311 29 14 26 12
Step 9: The HRV/ERV is now balanced, proceed
to secure both damper levers in place using
their locking screw. (Ref Fig 11.7) Seal the four (4)
balancing pressure taps with the nylon knock out
seals removed in Step 4.
Fig 11.7
Fresh
Air
Stale
Air
Remove all four (4)
nylon knock out seals.
Do not discard.
Damper
Lever
Front
Stale
Air
HIGHHIGH HIGHHIGH
LOW
LOW LOWLOW
Damper
Lever
Front
Fresh
Air
Air Vicié Air frais
Enlever les quatre
(4) bouchons
à défoncer de nylon.
Ne pas les jeter.
HAUTHAUT
BAS
BAS
HAUT
HAUT
BAS
BAS
Levier
du registre
Devant
Air
vicié
Levier
du registre
Devant
Air
frais
Pressure / Pression Fresh air / Air frais Stale air / Air vicié
IN. W.G. Pascal CFM
L/s
CFM
L/s
PO. d’eau (Pa) PCM PCM
0.50 125 - - 161 76
0.53 132 - - 159 75
0.56 139 - - 156 74
0.59 147 - - 153 72
0.62 154 - - 149 70
0.65 162 - - 146 69
0.68 169 - - 142 67
0.71 177 - - 138 65
0.74 184 149 70 133 63
0.77 192 147 69 129 61
0.80 199 144 68 124 59
0.83 207 141 67 119 56
0.86 214 138 65 114 54
0.89 222 133 63 109 51
0.92 229 128 60 103 49
0.95 237 123 58 97 46
0.98 244 116 55 91 43
1.01 252 109 51 85 40
1.04 259 101 48 78 37
1.07 267 93 44 71 34
1.10 274 84 40 64 30
1.13 281 74 35 57 27
1.16 289 64 30 50 24
1.19 296 53 25 42 20
1.22 304 41 19 34 16
1.25 311 29 14 26 12
Step 10: Mark down the balanced air ow rates
information on a label including in the kit. Apply
the label to the HRV/ERV access door for future
reference (e.g. date, balance airow rate, your
name, phone number and business address).
For Balancing Charts,
- Refer to page 22 of this manual
CAUTION: When adjusting
the damper lever do not use
a drill or electric screwdriver,
use a standard screwdriver.
NOTE: Turning
the damper lever
counterclockwise will
reduce the airow,
turning clockwise will
increase the airow
NOTE: Turning
the damper lever
counterclockwise will
reduce the airow,
turning clockwise will
increase the airow