Note: Contact factory for network points list
Connection Type
The default CONNECTION TYPE for the BACnet over
ETHERNET to the WEB PORTAL is a CAT5 Cable via an
RJ-45 connector. The connector plugs into the Ethernet
10BaseT port.
Note: If these settings need to be changed, please contact a
ClimaCool Representative.
Ethernet Network
The Master Controller is equipped with an interface which
may be connected directly to the Ethernet network using
the 10BaseT port. To prevent circular routes, the Master
Panel will be congured only for BACnet/IP. The BACnet/IP
Network Number will be defaulted to 516800. The BACnet/
Ethernet router conguration will be disabled and the
Ethernet Network number set to 0.
Note: If these settings need to be changed, please contact a
ClimaCool Representative.
IP Address
The following is the default settings for the IP Address for a
typical Master Controller:
IP .............................................192.168.17.100
Subnet Mask...........................255.255.255.0
Gateway ..................................192.168.17.1
Note: If these settings need to be changed, please contact a
ClimaCool Representative.
Device Instance of Master Controller
The device instance number for the Master Controller is
516800. The “address” number of the Master is “01,” as
identied by the two rotary switches on the Master PCB
(one rotary switch is for 10’s digit and the other is for the 1’s
digit), (See Figure 1 – page 4).
Note: If these settings need to be changed, please contact a
ClimaCool Representative.
Device Instance of Module Controller
The device instance number for the FIRST Module
Controller is 243002. The “address” number of the FIRST
module controller is “02.” Similarly, the device instance
number of the SECOND Module Controller is 243003.
The “address” number of the SECOND Module Controller
is “03.”
CoolLogic Control System Network Setup