A 1” male NPT fitting is provided for the drain connection on the discharge port of the diverter
valve (lower, right-hand corner of machine). This fitting may be removed and user provided
hardware may be used if necessary to facilitate compliance with local plumbing codes. Code
requires that the drain discharge provides an air gap no less than 1” or two pipe diameters,
whichever is greater, above the flood level rim of an approved floor drain.
2.2.3. Post Instructions
Mount the wall chart provided in a conspicuous place and instruct the operators on proper cleaning
and operation of the L-1X and L-1X16. The instruction chart is also provided as an appendix to
this manual (see appendix).
2.2.4. Installers Checklist
Dishmachine checked for concealed damage
Hot water supply is 140° F (60 C)
Incoming water supply line is ½” minimum
Supply circuit breaker for machine is properly sized (20 amp)
Service voltage and phase type are correct to machine data plate
Drain hose is installed with adequate air gap
Dishmachine is properly grounded
Dishmachine is properly leveled
Machine circuit breaker is labeled “DISHWASHER”
Machine has been connected with correctly sized wire (12 gauge
minimum)