Adept Cobra PLC600/PLC800 Robot User’s Guide, Rev C 67
Figure 4-12. Optional Front Panel Schematic
Emergency Stop Circuits
The PLC Server provides connections for Emergency Stop (E-Stop) circuits on the XUSR
and XFP connectors. This gives the PLC Server system the ability to duplicate E-Stop
functionality from a remote location using voltage-free contacts. See Figure 4-11.
The XUSR connector provides external two-channel E-Stop input on pins 1 to 14 and 2 to
15. The XFP connector provides two-channel E-Stop input on pins 1 to 9 and 2 to 10.
NOTE: These pins must be shorted if not used. Both channels must open
independently if used. Although an Emergency Stop will occur, the PLC
Server will malfunction if one channel is jumpered closed and the other
channel is opened. It will also malfunction if the channels are shorted
together.