Field Wiring the -48 Vdc Power Inverter
C–2
AlphaServer Intelligent Peripheral Platform Hardware Owner's Guide
C.1.1
Installing Suitable Field Wiring
The following subsections describe how to install suitable field wiring.
C.1.1.1 Field Wiring Recommendations
Table C–1 lists the field wiring recommendations for each side of the -48 Vdc power
controller. The -48 Vdc power controller has dual power feeds.
Table C–1: Field Wiring Recommendations for Each Power Feed
Input Power Requirement -48 Vdc Power Controller
Input voltage -48 Vdc
Input current 50 A max
Inrush peak 6 A max soft start limited
Recommended wire: Wire should be U/L recognized and CSA certified for 105°C (221°F),
with insulation rated for 600 Vac. Each of the 3-wire conductors should be a minimum of 6
AWG stranded.
____________________________WARNING_________________________
High energy hazard. Proper precautions required.
______________________________________________________________
___________________________ VORSICHT ________________________
Hochspannungsgefahr. Geeignete Vorsichtsmaßnahmen sind notwendig.
______________________________________________________________
C.1.1.2 Installing the Wiring
1.
Strip the wire insulation to approximately 1.27 cm (.50 in.).
2.
Insert the wire into the terminal block as follows:
a.
Observe the wire color/polarity
Black: -48 Vdc
White: +48 Vdc
Green/yellow: Ground
b.
Torque the #10-32 compression screws to 40 to 45 inch-pounds.
______________________________ Note ___________________________
Refer to the DIGITAL 2T-48VDC-xx -48Vdc-to-120Vac Power Inverter Owner’s
Guide for information on powering up and testing the -48 Vdc inverter.