User guide

NT® INTEGRATED FLOW CONTROLLER WITH DEVICENET™ COMMUNICATION USER GUIDE
30 Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300 ENTEGRIS, INC.
SERVICES 3.1 - INSTANCE SERVICES - DEVICENET™ OBJECT 1
PARAMETER
CODE REQUIRED
SUPPORTED
NAME PARAMETERS DESCRIPTION VALUES
0E
hex
Required Yes Get_Attribute_ Attribute ID Retrieves an 1–255
Single (USINT) attribute value
10
hex
Required Yes Set_Attribute_ Attribute ID Sets an Attribute ID = 1–255
Single (USINT); Value attribute value Value = attribute
specific
4B
hex
Required Yes Allocate_Master/ Allocation Initializes 0 × 01= Explicit
Slave_Connection choice; Master predefined 0 × 02 = Poll
_Set master/slave 0 × 03= Both
connection set
4C
hex
Required Yes Release_Group_2 Allocation Releases 0 × 01= Explicit
_Identifier_Set choice predefined 0 × 02 = Poll
master/slave 0 × 03 = Both
connection set
SERVICES DATA FIELD PARAMETERS
PARAMETER REQUIRED DATA TYPE DESCRIPTION VALUES
Allocation choice Yes BYTE Specifies the b0 = Explicit
connection types b1 = Polled
b2 = Bit strobe
b3 = Multicast poll
b4 = COS
b5 = Cyclic
b6 = Ack suppress
b7 = Reserved
Master Yes USINT Master's MACID = 0-63
Allocate success Yes BYTE Message body format 0 = 8/8 [default]
response (number of bits for 1 = 8/16
Class/Instance identifiers) 2 = 16/16
3 = 16/8
Assembly Object (04
hex
)
Class
ATTRIBUTES 4.0 - CLASS ATTRIBUTES - ASSEMBLY OBJECT
ATT. RE- SUP- ACCESS DATA ATTRIBUTE
ID QUIRED PORTED RULE NV NAME TYPE DESCRIPTION VALUES
1 Optional Yes Get NVC Revision UINT Object revision = 02
100 Vendor Yes Set NV Default USINT Default output = 10, 11
specific I/O consume assembly inst ID [default] = 10
101 Vendor Yes Set NV Default USINT Default input = 1, 2, 3, 6
specific I/O produce assembly inst ID [default] = 2
ENT48906 10/15/04 8:12 AM Page 30