User guide

ENTEGRIS, INC. Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300 31
NT® INTEGRATED FLOW CONTROLLER WITH DEVICENET™ COMMUNICATION USER GUIDE
SERVICES 4.0 - CLASS SERVICES - ASSEMBLY OBJECT
RE- SUP- PARAMETER
CODE QUIRED PORTED NAME PARAMETERS DESCRIPTION VALUES
0E
hex
Required Yes Get_Attribute_ Attribute ID Retrieves an 1–255
Single (USINT) attribute value
10
hex
Required Yes Set_Attribute_ Attribute ID Sets an Attribute ID = 1–255
Single (USINT); Value attribute value Value = attribute
specific
Instances
Instance Identifiers
4.N ASSEMBLY OBJECT INSTANCES
NUMBER REQUIRED TYPE ELEMENTS
1 Y Input Flow
2 Y (default) Input Status and flow
3 N Input Status, flow and pressure
6 N Input Status, flow, pressure and valve
10 Y (default) Output Set point
11 Y Output Override and set point
ASSEMBLY OBJECT ELEMENT MAPPING
DATA COMPO-
CLASS
INSTANCE
ATTRIBUTE
NENT NAME NAME NUMBER NUMBER NAME NUMBER TYPE
Flow S-Analog sensor 31
hex
1 Value 6 INT
Pressure S-Analog sensor 31
hex
2 Value 6 INT
Valve S-Analog actuator 32
hex
1 Value 6 INT
Override S-Analog actuator 32
hex
1 Override 5 USINT
Set point S-Single stage
controller 33
hex
1 Set point 6 INT
Status S-Device 30
hex
1 Exception 12 BYTE
supervisor status
Element Mapping