NT® INTEGRATED FLOW CONTROLLER WITH DEVICENET™ COMMUNICATION USER GUIDE
36 Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300 ENTEGRIS, INC.
Instance 1
ATTRIBUTES 30.1 - INSTANCE ATTRIBUTES - S-DEVICE SUPERVISOR OBJECT 1
ATT. RE- SUP- ACCESS DATA ATTRIBUTE
ID QUIRED PORTED RULE NV NAME TYPE DESCRIPTION VALUES
3 Required Yes Get NVC Device SHORT ASCII Text, Max. “FFC”
Type STRING 8 Characters,
see “Semantics”
section
4 Required Yes Get NVC SEMI SHORT Specifies the "E54-0997"
Standard STRING revision level
Revision of the SEMI S/A
Level Network Standard
to which the
device complies.
5 Required Yes Get NVC Manu- SHORT ASCII text, max. "NT International"
facturer’s STRING 20 characters
Name
6 Required Yes Get NVF Manu- SHORT ASCII text, max. "6500”
facturer’s STRING 20 characters
Model
Number
7 Required Yes Get NVC Software SHORT ASCII text, max. "x.xx" current
Revision STRING 6 characters Application Code
Level SW revision
8 Required Yes Get NVF Hardware SHORT ASCII text, max. "x.xx" current
Revision STRING 6 characters Controller Circuit
Level Board HW revision
9 Optional Yes Get NVF Manu- SHORT ASCII text, max. Device specific
facturer’s STRING 30 characters
Serial
Number
10 Optional Yes Get NVF Device SHORT ASCII text, max. Device specific
Configur- STRING 50 characters
ation
11 Required Yes Get V Device USINT State of the 0 = Undefined
Status device’s 1 = Self-testing
application 2 = Idle
objects 3 = Self-test exception
4 = Executing
5 = Abort
6 = Critical fault
7-50 = Reserved by
DeviceNet™
51-99 = Device specific
100-255 = Vendor specific
12 Required Yes Get V Exception BYTE Bitmapped b0 = Common alarm
Status summary of b1 = Device specific alarm
the exception b2 = Vendor specific alarm
detail bits b3 = Reserved
b4 = Common warning
b5 = Device specific
warning
b6 = Vendor specific
warning
b7 = 1
ENT48906 10/15/04 8:12 AM Page 36