NT® INTEGRATED FLOW CONTROLLER WITH DEVICENET™ COMMUNICATION USER GUIDE
38 Customer Service Tel. 763-502-0200 Customer Service Fax 763-502-0300 ENTEGRIS, INC.
ATT. RE- SUP- ACCESS DATA ATTRIBUTE
ID QUIRED PORTED RULE NV NAME TYPE DESCRIPTION VALUES
14 Based on Yes Get V Exception STRUCT of: A Structure of three
Exception Detail Structures contain-
Status b7 Warning ing bitmapped
representations of
the warning detail
Common STRUCT of:
Exception
Detail
Size USINT Number of common = 02
detail bytes
Detail [0] BYTE b0 = Internal
diagnostics
b1 = 0
b2 = EPROM
b3 = EEPROM
b4 = RAM
b5 = 0
b6 = Internal
real-time
b7 = 0
Detail [1] BYTE b0 : b7 =
Not supported
Device STRUCT of:
Exception
Detail
Size USINT Number of device = 03
detail bytes
Detail [0] BYTE b0 = Reading valid
b1 = Flow low
b2 = Flow high
b3 = 0
b4 = 0
b5 = 0
b6 = Pressure Low
b7 = Pressure High
Detail [1] BYTE b0 : b7 = 0
Detail [2] BYTE b0 : b7 = 0
Manu- STRUCT of:
facturer
Exception
Detail
Size USINT Number of = 01
manufacturer
detail bytes
Detail [0] BYTE Manufacturer b0 : b7 = 0
specified
15 Required Yes Set NV Alarm BOOL Enables the set- 00 = Disabled
Enable ting of alarm bits 01 = Enabled
[default]
16 Required Yes Set NV Warning BOOL Enables the set- 00 = Disabled
Enable ting of warning 01 = Enabled
bits [default]