Installation guide

62
www.cooperbussmann.com/BussmannWirelessResources
Cooper Bussmann BU-905U-L Wireless I/O Configuration Manual
Featur
e Description Example
Unit Temp Warm-Up Time The amount of time the analog circuits are turned on before
sampling the internal temperature sensor.
You should always set this value set to the minimum value
(0.08 seconds).
Supply Voltage Sample Period Time between samples of the internal supply voltage.
Ain1 Debounce The debounce time is the product of the number of samples
and the sample period. The signal must differ from the previous
value by the sensitivity value for this duration to register a
‘change of state.’
This means that changing the analog sample time will also
change the debounce time. For analog signals, a value of
0 or 1 generates the quickest response; 255 generates the
slowest response.
Ain1 Sample Period Sets the period between samples of the thermocouple input.
A smaller value will cause mappings using this input to be
triggered more frequently (i.e., quicker response).
A larger value will cause mappings using this input to be
triggered less frequently (less power consumption).
3A1579Rev1.4