User guide

SET UP INSTRUCTIONS using a low temp board as a high
Parameter Display Min. Max. Freezer
Set-point +1ºc/+4ºc
Temperature set-point C1 Set-point Deg. .
0
C 1
Operating parameters
Temp.differential P1 0 Deg.
0
C 7 Deg.
0
C 3
Probe offset P2 -10 Deg.
0
C 7 Deg.
0
C 0
Set point maximum P3 -63 Deg.
0
C 31 Deg.
0
C 5
Set point minimum P4 -63 Deg.
0
C 31Deg.
0
C 1
Comp. rest time P5 0 minutes 20 minutes 2
Defrost parameters
Defrost per day D1 0 24 4
Termination temp. D2 0 Deg.
0
C 31 minutes 15
Termination time. D3 0 minutes 31 minutes 15
Defrost type: 0=Elect;1=Gas D4 0 1 0
Drain Down time D5 0 minutes 7 minutes 2
Fan Delay Time D6 0 minutes 15 minutes 0
Recovery time D7 0 minutes 15 minutes 10
Fan Delay term.temp. D8 -20 Deg.
0
C 0 Deg.
0
C -1
Alarm parameters
Alarm duration A1 0 minutes 61 minutes 15
0= buzzer muted
61=buzzer continuous
High temp.alarm offset A2 -63 Deg.
0
C 0 Deg.
0
C 10
Low temp.alarm offset A3 -63 Deg.
0
C 0 Deg.
0
C 10
Alarm delay A4 0 minutes 60 minutes 30
1. Disconnect defrost solenoid and drip tray heater (on printed circuit board terminals 3).
2. Remove evap fan live from terminal 2 and put on to L terminal.
3. Disconnect door heater from L terminal.