User guide

GP or RDM Controller PARAMETERS
Parameter Display Min. Max. Low High
Set-point
–5
0
C/-2
0
C +5
0
C/+8
0
C
Temperature set-point C1 Set-point Deg. .
0
C -5 5
Operating parameters
Temp.differential P1 0 Deg.
0
C 7 Deg.
0
C 3 3
Probe offset P2 -10 Deg.
0
C 7 Deg.
0
C 0 0
Set point maximum P3 -63 Deg.
0
C 31 Deg.
0
C -1 9
Set point minimum P4 -63 Deg.
0
C 31Deg.
0
C -6 4
Comp. rest time P5 0 minutes 20 minutes 2 2
Defrost parameters
Defrost per day D1 0 24 4 4
Termination temp. D2 0 Deg.
0
C 31 minutes 15 15
Termination time. D3 0 minutes 31 minutes 20 20
Defrost type: 0=Elect;1=Gas D4 0 1 0 0
Drain Down time D5 0 minutes 7 minutes 1 1
Fan Delay Time D6 0 minutes 15 minutes 5 5
Recovery time D7 0 minutes 15 minutes 10 10
Fan Delay term.temp. D8 -20 Deg.
0
C 0 Deg.
0
C -1 -1
Alarm parameters
Alarm duration A1 0 minutes 61 minutes 15 15
0= buzzer muted
61=buzzer continuous
High temp.alarm offset A2 -63 Deg.
0
C 0 Deg.
0
C 10 10
Low temp.alarm offset A3 -63 Deg.
0
C 0 Deg.
0
C 10 10
Alarm delay A4 0 minutes 60 minutes 30 30