Installation Manual

18
Gas shutoff valve:
A manual gas line shut-off valve must be installed in an easily accessible
location. Do not block access to shut-off valve. The valve is for turning on or
shutting off gas to the range.
GAS PRESSURE REGULATOR
The gas pressure regulator supplied with this range must be used. The inlet
pressure to the regulator should be as follows for proper operation:
Natural gas LP gas
Minimum pressure 4" WCP 10" WCP
Maximum pressure 7" WCP 11" WCP
Contact local gas supplier if you are not sure about the inlet pressure.
Burner Input Requirements
Input ratings shown on the model/serial rating plate are for elevations up to
2,000 ft (609.6 m).
For elevations above 2,000 ft (609.6 m), ratings are reduced at a rate of 4%
for each 1,000 ft (304.8 m) above sea level (not applicable for Canada).
GAS SUPPLY PRESSURE TESTING
Gas supply pressure for testing regulator must be at least 1" (2.5 cm) water
column pressure above the manifold pressure shown on the model/serial
rating plate.
Line pressure testing above 0.5 psi gauge (14" WCP)
The range and its individual shutoff valve must be disconnected from the gas
supply piping system during any pressure testing of that system at test
pressures in excess of 0.5 psi (3.5 kPa).
Line pressure testing at 0.5 psi gauge (14" WCP) or lower
The range must be isolated from the gas supply piping system by closing its
individual manual shutoff valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).