Installation Manual

40
2. OVP Recovery <FUNC1>When the DC input voltage is higher than the
OVP setting, the SD-series shuts-down; once the input voltage falls below
the set OVP value, the SD-series will automatically restart.
Default = 15 VDC @ 12V Model, 30 VDC @ 24V Model, 60 VDC @ 48V
Model
Model
Setting value range
12 V
13 VDC ~ 15 VDC
24 V
26 VDC ~ 30 VDC
48 V
52 VDC ~ 60 VDC
Table 30. OVP Recovery <FUNC1>
3. UVP Setting <FUNC2>Setting Under Voltage
Protection (UVP) and Shut-down on the inverter operation.
Default = 10 VDC@ 12V Model, 20 VDC @ 24V Model, 40VDC @ 48V
Model
Model
Setting value range
12 V
10.0 VDC ~ 12.5 VDC
24 V
20.0 VDC ~ 25.0 VDC
48 V
40.0 VDC ~ 50.0 VDC
Table 31. UVP Setting <FUNC2>
4. UVP Recovery <FUNC3>When the DC input voltage is below the set UVP
value, the SD-series shuts-down; Once the input voltage rises above the set
UVP value, the SD-series will automatically restart.
Default = 12.5VDC @ 12V Model, 25 VDC @ 24V Model, 50VDC @ 48V
Model
Model
Setting value range
12 V
11.5 VDC ~ 13.5 VDC
24 V
23.0 VDC ~ 27.0 VDC
48 V
46.0 VDC ~ 54.0 VDC
Table 32. UVP Recovery <FUNC3>
5. UV Alarm <FUNC4>Setting Under Voltage (UV) alarm. When the input
voltage is lower than the set value, the SD-series will sound a “beep” to
remind you that the unit is going to shut-down.
Default = 10.5 VDC @ 12 V Model, 21 VDC @ 24 V Model, 42 VDC @ 48 V
Model
Model
Setting value range
12 V
10.5 VDC ~ 13.0 VDC
24 V
21.0 VDC ~ 26.0 VDC
48 V
42.0 VDC ~ 52.0 VDC
Table 33. UV Alarm <FUNC4>