SE350 User Manual

17
Model
Wire AWG
Inline fuse
SE350-124 / 224
#10
25 A
SE350-148 / 248
#14
12.5A
SE400-112 / 212
#10
60A
SE400-124 / 224
#14
30 A
SE400-148 / 248
#18
15 A
Table 16. SE series cable size
Note
Batteries are capable of providing very large currents in
case of short circuit. The fuse should be as close to the
positive battery terminal as possible. Use Bussmann ANN
series fuses (will also require Fuse Block 4164) or
equivalent.
3-2-2. Green Terminal
Item
Description
1
GND
2
Enable (ENB)
3
Enable (ENB)
Table 17. SE series green terminal description
Figure 9. SE series green terminal
Note
Fault conditions include Input under / over voltage, output short
circuit / over load, over / under temperature.
Caution!
Please follow the following steps for the installation.
Before installing the inverter, make sure the main switch is at “OFF”
position.
Before using the remote function, make sure the main switch pressed
toward “REMOTE”.
Use 20 ~ 24 #AWG wire to connect the remote control terminals.