SP1500 Manual

33
Function Command and description
BIT8
0:No OTP Protection
1: OTP Protection
BIT9
0:No UTP Protection
1: UTP Protection
BIT10
0:No OLPH Protection
1: OLPH Protection
BIT11
0:No OLPL Protection
1: OLPL Protection
* Status definition refer to Table 36. Status definition
Query the SP series DC input
voltage of the battery
Format: VBAT?
Query the SP series output
power
Format: PINV?
Reset default Format:*RST
Select the Setup Menus with the
help of Function Codes
Format : FUNC <Function Code>
Function code Setting Menu
0OVP setting
1OVP Recovery
2 UVP Setting
3UVP Recovery
5 RS-232 Baud-rate
6Retry Time
Query the functions No Format: FUNC?
Query the setting value of the
function
Format: SETT?
Set or adjust the value of the
function
Format: SETT <value>
Table 34. RS-232 interface command
SP-700 ~ SP-2000 Status Definition
Description Definition
OLPL Protection OLPL: Over Load Protection Low (101~115%)
Sof Fail Protection Sof Fail: Soft Start Fail
Poff Protection Poff: Power off
UVP Protection UVP: Under Voltage Protection
OVP Protection OVP: Over Voltage Protection
OLPM Protection OLPM: Over Load Protection Middle (116~200%)
OLPH Protection OLPH: Over Load Protection High (>200%)
OTP Protection OTP: Over Temperature Protection
UTP Protection UTP: Under Temperature Protection
OOCP Protection OOCP: Output Over Current Protection
Table 35. SP-700 ~ SP-2000 Status Definition