Product Specifications

1000W Pure Sine Wave Inverter
SR1000T series
Voltage Range
18 ~ 34VDC 18 ~ 34VDC
No Load Current
1.4A
0.75A
1.3A
0.7A
36 ~ 68VDC
36 ~ 68VDC
36 ~ 60VDC (only UL)
36 ~ 68VDC
MODEL
SR1000T-124 SR1000T-148 SR1000T-224 SR1000T-248
Input
Voltage
24VDC 48VDC 24VDC 48VDC
Continuous Output Power
Maximum Output Power (3min)
Surge Power
Frequency
Output Voltage
Efficiency (Full Load)
1000W
1100W
2000W
47 ~ 63Hz 0.5% (User-selectable)±
97 ~ 123VAC (User-selectable)
194 ~ 246VAC (User-selectable)
87%
88%
90% 91%
Waveform
Pure Sine Wave (THD < 2%)
Output
LCD Panel
2-line LCD Panel
Input voltage level, output load level and faulty status
Signal & Control
LED Indicator
Dry Contact Terminal
By relay
Remote Control Port
RJ-11
Input Protection
Over / Under Voltage, Reverse Polarity (Fuse)
Short-Circuit, Overload, Over Temperature
Protection
AC Output Protection
AC Input Protection
12Amp Circuit Breaker
6Amp Circuit Breaker
REV. A0
12/09/22
1
Bypass Relay
Relay Specification
Bypass Relay Selectable
Switching Time
15Amp / 120VAC, 10Amp / 250VAC
On Line / Off Line (Haphazard, Normal, Exacting) selectable
From AC bypass mode (off-line mode): ≤ 20ms
From DC to AC inverter mode (on-line mode): 8ms (Exacting Mode)
Environment
Working Temp. (Full Load)
Storage
0°C ~ 50°C
-30 ~ 70°C°C
Certified EN 55022 Class B; EN 61000-3-2, -3-3;
EN 55024; IEC 61000-4-2, 3, 4, 5, 6, 8, 11
Safety & EMC
Safety Standards
EMC Standards
Certified FCC Class B
Certified UL 60950-1 Certified EN 60950-1
Failure Indication
Buzzer alarm and dry contact
Cooling
Thermal & Load control Fan
Packing
7.46kg; 2pcs/ 15.9kg/ 1.74CUFT
Dimension (WxHxD)
483x44x345 mm / 19.02x1.73x13.58 inch
Others
Application
Focus on Telecommunication (Base-station), Networking (Data Center) & Battery Backup Systems.
Pure Sine Wave output (THD )< 2%
Standard Rackmount191U
User-Friendly LCM Module
Dry contact for system alarm
RS- communication port232
Selectable On-line / Off-line modes
Built-in AC transfer switch and AC breaker
Hard-wire and dual AC outlet output connection
Fan failure alarm with buzzer
Input Protection: Reverse Polarity (Fuse) / Under Voltage /
Over Voltage
Output Protection: Short Circuit / Over Temperature
Features:
DATE
ECO
REV
APPROVED
REV. A3
15/12/15
1
A1
A2
A3
A4
36 ~ 60VDC (only UL)
2013/06/27
Pony/Fendi
2014/10/28
Freq. 0.05%修正為0.5%,單位與重量修改
Pony/
2015/12/15
安規與尺寸修改
Pony/

Summary of content (1 pages)