Technical data

Chapter 3 Installation
14
for the AC cables and grounding cable.
ABConduit for DC cables
C: Conduit for communication cables
D: Conduit for AC cables
E: Conduit for the grounding cable
(c) Punch holes on the bottom cover for the conduits;
(d) Check the seal of the cover;
(e) Restore the cover to the equipmentattach the
screws;
(f) Insert the conduits into the openings;
(g) Attach the conduits with the appropriate hubs.
3.4.1 DC connection
(1) The following rules should be abided by to ensure
the highest efficiency of the PV inverter:
(a) First, make sure that the maximum open circuit
voltage of the PV modules is lower than 600Vdc
under any conditions;
(b) Ensure that the polarity of DC input is correct, i.e.
the positive pole of PV module is connected to the
positive pole of the inverter’s DC input, and the
negative pole of PV module is connected to the
negative pole of the inverters DC input;
(c) The Max. DC input current of the inverter is 350A,
so 35 95mm
2
copper core cables with an
insulation rating of 90 are recommended for
inverter’s DC input, as shown in Table 3-2