Technical data

40
Chapter 5 Operation
Warn/Protect/
Fault
Definition Possible causes
Recommended
solutions
2
GridV.OutLim
Grid voltage
exceeds the
specified range,
or grid is not
detected
1Grid voltage is
abnormal;
2Power grid
outage
3Cable
connection
between the
inverter and the
grid is
disconnected
1Observe for 10
minutes and see
whether the alarm will
be eliminated
automatically;
2Check whether the
grid voltage is within the
specified range;
3Check whether the
cable connection to the
grid is disconnected or
has abnormalities;
4Contact after-sales
service personnel
3GridF.OutLim
Grid voltage
frequency is
abnormal, or grid
is not detected
1Grid frequency
has abnormalities;
2Power outage of
the grid;
3Cable
connection
between the
inverter and the
grid is
disconnected
1Observe for 10
minutes and see
whether the alarm will
be eliminated
automatically;
2Check whether the
grid frequency is within
the specified range;
3Check whether the
cable connection to the
grid is disconnected or
has abnormalities;
4Contact after-sales
service personnel
4PV.VoltOver
PV voltage
exceeds the
specified value
PV over-voltage
1Observe for 30
minutes and see
whether the alarm will
be eliminated
automatically;
2Check whether PV
voltage exceeds the
specified range;
3Turn off the PV input
switch, wait for 5
minutes, turn on the
switch again;