Technical data

58
Chapter 6 Human Machine Interface
Figure 6-11 System parameter setup
Table 6-3 Protection Parameters Table
No.
Description of
parameter
LCD indication
Setup range (lower
limit, default & upper
limit)
1
Grid voltage upper
limit (V)
GridV.Max(V) 527, 527, 575
2
Trip time under
Max. voltage (S)
GridVmaxTripT(S) 0.16, 1.00, 1.00
3
Grid votage lower
limit (V)
GridV.Min(V) 240, 422, 422