Technical data

Chapter 7 Technical Data
61
Power consumption overnight <50W
Certification
General Standard UL1741 Rev 2010, IEEE1547,
Radiated Emission FCC PART15, Class A
Display and communication
Standard Communication
RS485
Optional Communication
Ethernet
Fault Alarm
Dry contact (MAX 240VAC, 2A)
Display
LCD Display
Mechanical parameters
WxDxH(mm) 1200×1850×880
Weight (kg) 900kg
*Note 1: Exceeding the rated voltage shown in “Maximum
DC voltage” may cause permanent damage to the
equipment.
**Note 2: “Allowable Grid Voltage” and “Nominal grid
frequency” depend on the specific national grid standard.
***Note 3: When the ambient temperature exceeds 50 , the
maximum output power will derate as 3% per . When the
ambient temperature reaches 60 , the maximum output
power will be 70% of the rated output power. The inverter will
stop running under self-protection when the ambient
temperature is over 65 .