Technical data

Chapter 3 Installation
25
Figure 3-14 Diagram for wire stripping of AC output
(c) Crimp the terminal as shown in Figure 3-15:
Figure 3-15 Diagram for terminal crimping of AC output
(d) Connect the L1, L2, L3 and Neutral (red, black,
blue, grey) AC output wires to the corresponding
terminals on the PCB board.
(3) Wire connection for grounding:
(a) The Gnd wire (Equipment grounding conductor) is
recommended to be green or green with
continuous yellow stripes, per National Electrical
Code. Insert the cable through the steel conduit
and strip the skin 0.4 inch off the cables as shown
in Figure 3-16:
Figure 3-16 Diagram for wire stripping of grounding conductor
(b) Crimp the terminal with the ring terminal in the