Technical data
Chapter 5 Human Machine Interface
49
Table 5-3 Protection Parameters Table
No. Description of parameter
Setup range (lower limit, default
& upper limit)
1
Grid line voltage upper limit
(200, 528, 533V)
2
Trip time under Max. Grid V.
(0.05, 1.80, 2.00S)
3
Grid line voltage lower limit
(0, 422, 480V)
4
Trip time under Min. Grid V.
(0.05,1.80,2.00S)
5
Grid frequency upper limit
(50.00,60.50,65.00Hz)
6
Grid frequency lower limit
(45.00,59.30,60.00Hz)
7
Trip time under Min. Grid F.
(0.05,0.08,300.00S)
8
Insulation impedance lower limit
(200,600,1200KΩ)
9*
Active power derating
(80.0%,100.0%,100.0%)
10*
Reactive power compensation
(-0.900,1.000,0.900)
Note: The function of active power derating and
reactive power compensation is optional. For detailed
information, you may call our after-sales service center.
(2) “2 Restart” menu. If an internal fault shutdown
happens, a severe fault has occurred inside the inverter. The
user may perform a force restart once in this menu if the user
needs to restart the inverter.
Note: this function is effective only when the fault
“IntFaultA~O” in the troubleshooting table occurs.
The inverter may restore to normal operation
automatically if alarm or protection faults occur.