Instruction Manual

10
1111
DSC Series
2.0 Installation Heater Mounting Recommended Mounting Heights
Figure 2.2 Heater Orientation
Chart 2.1 Recommended Mounting Heights
Level end to end
Optional
Mounting
Bracket
0-3
End
End
NOTE: This chart is provided as a guideline. Actual conditions dictate variances from this data.
Recommended Mounting Heights
WARNING
!
Heater must be installed at least 6.5 feet above the finished floor.
BTU/h
Recommended
Mounting Height
Approximate
Coverage Area
Approx. Coverage
(sq. ft.)
31,000 8’-0” to 12’-0” 8’ x 8’ 64 sq. ft.
34,000 8’-6” to 13’-0” 9’ x 9’ 81 sq. ft.