Appendix “B”
PRESSURE DROP TABLE (See INDEX: “Gas Connections” for further details).
The BTU’s for each appliance are listed in the
tables below for reference. Find the maximum
BTU requirements for the appliance(s) purchased
adding the combined BTU’s together. Cross
reference the total BTU’s against “Table 3” to
determine the maximum allowable supply line
length for the BTU’s required. If the supply line
length available does not support the BTU
requirements, the pipe size will need to be
changed accordingly. Please contact a certified
gas technician for additional size options.
BTU Grills: Table 1
BTU’s
LP Pilot
Orifice - 70
BTU’s
LP Burner
Orifice - 58
BTU’s
NG Pilot
Orifice - 57
BTU’s
NG Burner
Orifice - 51
Total BTU’s
NG/LP
IBI30
5,500
14,750
5,500
14,750
64,500
IBI36
5,500
14,750
5,500
14,750
79,250
IBI42
5,500
14,750
5,500
14,750
94,000
IBI48
5,500
14,750
5,500
14,750
108,750
IBI482RD
5,500
14,750
5,500
14,750
94,000
IGM24
5,500
14,750
5,500
14,750
49,750
IGM36
5,500
14,750
5,500
14,750
79.250
IGM42
5,500
14,750
5,500
14,750
94,000
IE30
5,500
14,750
5,500
14,750
64,500
IE36
5,500
14,750
5,500
14,750
79,250
IE42
5,500
14,750
5,500
14,750
94,000
IE36I (GRILL)
5,500
14,750
5,500
14,750
79,250
BTU Side Burners: Table 2
BTU’s
LP Burner
Orifice - 58
BTU’s
NG Burner
Orifice - 52
Total BTU’s
NG/LP
IBISB
12,000
12,000
24,000
IBISC-SB
12,000
12,000
24,000
ICM-SB
12,000
12,000
24,000
IE36I (SB)
12,000
12,000
24,000
Maximum Runs for All Appliances
on a supply Line: Table 3
Run Length
3/4 Pipe (in feet)
Max BTU for All
Appliances on Line
10
360,000
20
245,000
30
198,000
40
169,000
50
150,000
60
135,000
70
123,000
80
115,000